ABB REC670 Product Manual page 87

Bay control version 2.2
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Bay control REC670 2.2
Product version: 2.2.1
Table 70. Local acceleration logic ZCLCPSCH
Function
Operate current, LoadCurr
Operate current, MinCurr
Delay time on pick-up for current release
Delay time on drop-off for current release
Delay time on pick-up for MinCurr value
Table 71. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
Function
Operate mode of WEI logic
Operate voltage 3U0 for WEI trip
Operate time for current reversal
logic
Delay time for current reversal
Coordination time for weak-end
infeed logic
ABB
GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1
Range or value
(1–100)% of IBase
(1–100)% of IBase
(0.000–60.000) s
(0.000–60.000) s
(0.000–60.000) s
M16051-2 v11
Range or value
Off
Echo
Echo & Trip
(5-70)% of UBase
(0.000-60.000) s
(0.000-60.000) s
(0.000–60.000) s
Accuracy
±1.0% of I
r
±1.0% of I
r
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
±0.2% or ±35 ms whichever is greater
Accuracy
-
±0.5% of U
r
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
±0.2% or ±30 ms whichever is greater
1MRK 511 404-BEN A
87

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents