USING THE PROGRAM

BACnet Setting (ACP BACnet, AC Smart BACnet Only)

The following explains BACnet setting of ACS IV Controller.
Item
Temperature Unit
Setting
Device ID Setting
Vnet Number Setting
Register as Foreign
Device
Only Monitoring Setting
BACnet Port
To set the temperature unit communicating with BMS.
To designate the Device Instance Number, Device ID must be set.
Default Device ID is 9000, Device Instance Number is designated as
below.
y Indoor unit : Device ID
y ERV : Device ID + 1
y AHU : Device ID + 2
y Outdoor unit cycle information : Device ID + 3
y AWHP : Device ID + 4
y General : Device ID + 5
To use Modbus TCP function of ACP BACnet, Vnet Number must be set.
Set Vnet Number is used to Slave ID Address of Modbus TCP.
To register Foreign Device.
For more information, please consult with the experts of BMS.
When set to Enable the BMS has Read Only permission on this
device. Uncheck if BMS is required to have Read & Write permission.
To change the BACnet IP port. Default port is 47808.
For more information, please consult with the experts of BMS.