GE L90 Instruction Manual page 605

Ur series line current differential system
Hide thumbs Also See for L90:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 27 of 59)
ADDR
REGISTER NAME
65DD
Power Swing Detect Middle Left Blinder
65DE
Power Swing Detect Inner Right Blinder
65DF
Power Swing Detect Inner Left Blinder
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
66A0
Sensitive Directional Power 1 Function
66A1
Sensitive Directional Power 1 Signal Source
66A2
Sensitive Directional Power 1 RCA
66A3
Sensitive Directional Power 1 Calibration
66A4
Sensitive Directional Power 1 STG1 SMIN
66A5
Sensitive Directional Power 1 STG1 Delay
66A6
Sensitive Directional Power 1 STG2 SMIN
66A7
Sensitive Directional Power 1 STG2 Delay
66A8
Sensitive Directional Power 1 Block
66A9
Sensitive Directional Power 1 Target
66AA
Sensitive Directional Power 1 Events
66AB
Reserved (5 items)
66B0
...Repeated for Sensitive Directional Power 2
Load Encroachment (Read/Write Grouped Setting)
6700
Load Encroachment Function
6701
Load Encroachment Source
6702
Load Encroachment Minimum Voltage
6703
Load Encroachment Reach
6704
Load Encroachment Angle
6705
Load Encroachment Pickup Delay
6706
Load Encroachment Reset Delay
6707
Load Encroachment Block
6708
Load Encroachment Target
6709
Load Encroachment Events
670A
Reserved (6 items)
Trip Output (Read/Write Setting)
67E0
Trip Mode
67E1
Trip 3-Pole Input1
67E2
Trip 3-Pole Input2
67E3
Trip 3-Pole Input3
67E4
Trip 3-Pole Input4
67E5
Trip 3-Pole Input5
67E6
Trip 3-Pole Input6
67E7
Trip 1-Pole Input1
67E8
Trip 1-Pole Input2
67E9
Trip 1-Pole Input3
67EA
Trip 1-Pole Input4
67EB
Trip 1-Pole Input5
67EC
Trip 1-Pole Input6
67ED
Trip Reclose Input1
67EE
Trip Reclose Input2
67EF
Trip Reclose Input3
67F0
Trip Reclose Input4
67F1
Trip Reclose Input5
67F2
Trip Reclose Input6
67F3
Trip Force 3-Pole
67F4
Trip Pilot Priority
67F5
Breaker Phase A Open
67F6
Breaker Phase B Open
67F7
Breaker Phase C Open
GE Multilin
RANGE
0.1 to 500
0.1 to 500
0.1 to 500
0 to 1
0 to 5
0 to 359
0 to 0.95
-1.2 to 1.2
0 to 600
-1.2 to 1.2
0 to 600
---
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0.02 to 250
5 to 50
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
ohms
0.01
F001
ohms
0.01
F001
ohms
0.01
F001
---
1
F102
---
1
F167
degrees
1
F001
degrees
0.05
F001
pu
0.001
F002
s
0.01
F001
pu
0.001
F002
s
0.01
F001
---
---
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F195
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
DEFAULT
10000
10000
10000
0 (Disabled)
B
0 (SRC 1)
0
0
100
50
100
2000
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
250
100
30
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0