5 SETTINGS
c) TRIP AND ALARM LEDS
PATH: SETTINGS
PRODUCT SETUP
TRIP & ALARM LEDS
MESSAGE
The Trip and Alarm LEDs are on LED Panel 1. Each indicator can be programmed to become illuminated when the
selected FlexLogic™ operand is in the Logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
LED 1
MESSAGE
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the Logic 1 state.
LEDs 1 through 24 inclusive are on LED Panel 2; LEDs 25 through 48 inclusive are on LED Panel 3.
Refer to the LED Indicators section in chapter 4 for the locations of these indexed LEDs. These settings select the Flex-
Logic™ operands that control the LEDs. Support for applying user-customized labels to these LEDs is provided. If the
setting is "Self-Reset" (the default setting), the LED illumination will track the state of the selected LED operand.
1(48) TYPE
If the
setting is 'Latched', the LED, once lit, remains so until reset by the faceplate RESET button, from a
LED 1(48) TYPE
remote device via a communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–2: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
PARAMETER
LED 1 Operand
SETTING GROUP ACT 1
LED 2 Operand
SETTING GROUP ACT 2
LED 3 Operand
SETTING GROUP ACT 3
LED 4 Operand
SETTING GROUP ACT 4
LED 5 Operand
SETTING GROUP ACT 5
LED 6 Operand
SETTING GROUP ACT 6
LED 7 Operand
Off
LED 8 Operand
Off
LED 9 Operand
BREAKER 1 OPEN
LED 10 Operand
BREAKER 1 CLOSED
LED 11 Operand
BREAKER 1 TROUBLE
LED 12 Operand
Off
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
GE Multilin
USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off
USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
SETTING
LED 13 Operand
LED 14 Operand
LED 15 Operand
LED 16 Operand
LED 17 Operand
LED 18 Operand
LED 19 Operand
LED 20 Operand
LED 21 Operand
LED 22 Operand
LED 23 Operand
LED 24 Operand
D30 Line Distance Relay
5.2 PRODUCT SETUP
TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
PARAMETER
Off
BREAKER 2 OPEN
BREAKER 2 CLOSED
BREAKER 2 TROUBLE
SYNC 1 SYNC OP
SYNC 2 SYNC OP
Off
Off
AR ENABLED
AR DISABLED
AR RIP
AR LO
5