Mitsubishi Electric Q01UCPU User Manual page 123

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(5) Latch setting
To latch data, a latch range and timing need to be set.
(a) Latch range setting
Latch-target devices and ranges are set. There are two range settings: the latch clear operation enable range
setting (Latch (1)) and the latch clear operation disable range setting (Latch (2)).
Project window
Set the start and end device numbers.
● If "Use the same file name as the program" is selected in the PLC File tab of the PLC parameter dialog box, latch ranges
of the file register (ZR), extended data register (D), and extended link register (W) cannot be set. (All data in the file
register (ZR) will be held.) The data outside the latch range will be cleared when the CPU module is powered off and on
or is reset.
● When the file register file used is switched with the QDRSET instruction, the latch range setting of the file register will be
disabled. After switching, regardless of the latch range setting, all data in the file register will be held.
(b) Latch interval setting (High-speed Universal model QCPU only)
A latch timing is set. (
Project window
[Parameter]
[PLC Parameter]
Page 444, Appendix 1.2.8)
[Parameter]
[PLC Parameter]
CHAPTER 3 FUNCTIONS
Device
tab
"
"
Device
tab
"
"
3
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents