Data Logger - GE 845 Instruction Manual

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

DEVICE

Data Logger

NOTE:
4–66
TRIGGER ON TRIP:
Range: On, Off
Default: Off
Selecting the "On" setting enables triggering of the recorder when any of the protection
elements configured as a "Trip" function operates, or the state of the operand assigned
to operate the #1 Trip output relay changes to "high".
TRIGGER ON ALARM:
Range: On, Off
Default: Off
Selecting "On" setting enables triggering of the recorder when any of the protection
elements configured as "Alarm", or "Latched Alarm" function operates, or the state of the
operand assigned to trigger the Alarm LED changes to "high".
DIGITAL INPUT 1 to 32:
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
ANALOG INPUT 1 to 16:
Range: Off, Any analog parameter from the list of FlexLogic analog parameters.
Default: Off
The data logger samples and records up to 16 analog parameters at rate defined by the
user. All data is stored in non-volatile memory, where the information is retained upon a
relay control power loss.
The data logger can be configured with a few channels over a long period of time, or with
larger number of channels for a shorter period of time. The relay automatically partitions
the available memory between the channels in use.
The selection of the rate for logging data also affects the duration of recorded data. The
data logger has longer duration for sampling rates at longer periods of time (i.e. "1 minute",
"30 minutes", "1 hour"), as compared to sampling rates at short periods (i.e. "per cycle", or
"per second").
The recorded data can be downloaded to 8 Series EnerVista program and displayed with
parameters on the vertical axis and time on the horizontal axis.
If data is not available for the entire duration of pre-trigger, the trigger position will be
based on available pre-trigger.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents