Parameter window - Gx Functions

In this parameter window, additional functions of the output can be enabled.
The DLR/S features the option of enabling two additional communication objects. These communication
objects are primarily intended for certain functions, which are often not required in parallel. For this reason,
the user has a free selection of choice two additional communication objects for their application.
The DLR/S does not check the plausibility of the parameterization. Accordingly, the same communication
object can be selected twice as can a communication object, which is completely unsuitable for its
function, for example the communication object Warning staircase lighting does not have a function
without Activate stairc. light./Status function.
Enable additional object 1
Enable additional object 2
Options:
With both these parameters, two additional communication objects can be enabled for the lighting group
that are useful for special applications.
No function: No additional communication object is enabled.
Burn-in lamps/Activate status: The communication object Burn-in lamps/Status is available for the
lighting group. Using this communication object, the burn-in of these individual lighting groups can be
initiated, and the status can be read out or sent on the KNX. A prerequisite is that the function Burn-in
is selected in the
under this parameter.
86 2CDC 507 100 D0202 | DLR/S 8.16.1M
No function
Burn-in lamps/Activate status
Block
Staircase light. permanent ON
Warning staircase lighting
Activate stairc. light./Status
Parameter window Gx
Group, page 67. The burn-in time must also be parameterized