5.2 PRODUCT SETUP
An example user display setup and result is shown below:
USER DISPLAY 1
USER DISPLAYS
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the
5
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items
are different.
NOTE
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
DIRECT I/O
5-68
DISP 1 TOP LINE:
Current X
DISP 1 BOTTOM LINE:
MESSAGE
Current Y
DISP 1 ITEM 1:
MESSAGE
6016
DISP 1 ITEM 2:
MESSAGE
6357
DISP 1 ITEM 3:
MESSAGE
0
DISP 1 ITEM 4:
MESSAGE
0
DISP 1 ITEM 5:
MESSAGE
0
Current X
Current Y
DIRECT I/O
DIRECT OUTPUT
DEVICE ID: 1
DIRECT I/O CH1 RING
MESSAGE
CONFIGURATION: Yes
DIRECT I/O CH2 RING
MESSAGE
CONFIGURATION: Yes
DIRECT I/O DATA
MESSAGE
RATE: 64 kbps
DIRECT I/O CHANNEL
MESSAGE
CROSSOVER: Disabled
CRC ALARM CH1
MESSAGE
CRC ALARM CH2
MESSAGE
UNRETURNED
MESSAGE
MESSAGES ALARM CH1
UNRETURNED
MESSAGE
MESSAGES ALARM CH2
B30 Bus Differential System
Shows user-defined text with first tilde marker.
~
A
Shows user-defined text with second tilde marker.
~
A
Shows decimal form of user-selected Modbus register
address, corresponding to first tilde marker.
Shows decimal form of user-selected Modbus register
address, corresponding to second tilde marker.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
Shows the resultant display content.
0.850
0.327 A
5.2.16 DIRECT INPUTS AND OUTPUTS
Range: 1 to 16 in steps of 1
Range: Yes, No
Range: Yes, No
Range: 64 kbps, 128 kbps
Range: Disabled, Enabled
See page 5–74.
See page 5–74.
See page 5–75.
See page 5–75.
5 SETTINGS