Device Profile; Appendix 1 - ABB COM600 Series User Manual

Dnp 3.0 serial master (opc) substation management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: ABB Oy Distribution Automation
Device Name: COM600 3.4
Highest DNP Level Supported:
For Requests: Subset Level 2
For Responses: Subset Level 2
Notable objects, functions, and/or qualifiers supported in
addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Additions to level 2 are shaded in the accompanying imple-
mentation tables.
Maximum Data Link Frame Size (octets):
Transmitted: <292
Received: (must be 292)
Maximum Data Link Re-tries:
[ ] None
[ ] Fixed at _______________________
[x] Configurable, range 0 to 10, Channel Enquiry Limit
Requires Data Link Layer Confirmation:
[ ] Never
[ ] Always
[ ] Sometimes. If 'Sometimes', when? ______________________________________________
[x] Configurable, Channel Link Layer Confirmations Enabled property
Requires Application Layer Confirmation:
66
COM600 series, Version 5.0
DNP 3.0 Serial Master (OPC) User's Manual

Appendix 1

Device profile

Table A1-1 The device profile describing the implementation of the DNP 3.0 master
protocol in COM600
Device Function:
[x] Master [ ] Slave
Maximum Application Fragment Size (octets):
Transmitted: <250 (Single fragments only)
Received : 2048
Maximum Application Layer Re-tries:
[ ] None
[ ]
[x] Configurable, range 0 to 5, IED Application Message Retries
property
1MRS756567

Advertisement

Table of Contents
loading

Table of Contents