<Frequency setting mode selection>
[Parameter setting]
Title

Note) When setting the frequency by an extension panel option, fmod/f207 is set to 0 or 3.
[Programmed value]
:
6
:
:
:
:
:
:
Function
Frequency setting mode selection 1
Frequencies are set by rotating the setting dial on the inverter. Like the position
of notches in a volume knob, the frequency setting value at the position of the
Setting dial 1
notch is saved.
The frequency setting value is set by
 Refer to section 3.2.2
A frequency command is set by means of external analog signals.
Terminal VIA
(VIA terminal: 0 –10Vdc)
 Refer to section 3.2.2 and 7.3
A frequency command is set by means of external analog signals.
Terminal VIB
(VIB terminal: 0 - +10Vdc or -10 - +10Vdc)
 Refer to section 3.2.2 and 7.3
Frequencies are set by rotating the setting dial on the inverter. Press the center
of the setting dial to save the frequency setting value.
Setting dial 2
The frequency setting value is set by
 Refer to section 3.2.2
RS485
Frequencies are set by RS485 communication from an external device.
communication
 Refer to section 6.38
UP/DOWN from
Frequencies are set by up/down commands from a terminal.
external logic input
 Refer to section 6.10.4
CANopen
Frequencies are set by CANopen communication from an external device.
communication
 Refer to "CANopen communication Instruction Manual E6581911".
Adjustment range
0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
keys on an extension panel option.
keys on an extension panel option.
F-14
E6582175
Default setting
0