Configuration and operation
4.9 STEP 7 configuration
Resetting the trigger tag in the bit memory area / DB:
If the memory area of a trigger tag is in the bit memory or in a data block, the CP resets
the trigger variable itself to 0 (zero) as soon as the value of the data point has been
transferred. This can take up to 500 milliseconds.
Note
Fast setting of triggers
Triggers must not be set faster than a minimum interval of 500 milliseconds. This also
applies to hardware triggers (input area).
Note
Hardware trigger
You need to reset hardware triggers via the user program
Transferring the value of a data point configured as an event
You specify whether the value of a data point is transferred to the communications partner
immediately after the trigger fires or after a delay in the "Transmission mode" parameter.
Transmission mode
The transmission mode of a frame is set in the "Trigger" tab of the data point. With the
option, you specify whether messages of events are sent immediately or following a delay:
● Immediate transfer - Spontaneous
The value is transferred immediately.
● Buffered transfer - Conditionally spontaneous
The value is transferred only when one of the following conditions is fulfilled:
– The communications partner queries the station.
– The value of another event with the transmission mode "Spontaneous" is transferred.
4.9.7.8

Threshold value trigger

Note
Threshold value trigger: Calculation only after "Analog value preprocessing"
Note that the analog value preprocessing is performed before the check for a configured
threshold value and before calculating the threshold value.
This affects the value that is configured for the threshold value trigger.
Note
No Threshold value trigger if Mean value generation is configured
If mean value generation is configured, no threshold value trigger can be configured for the
analog value event involved.
74
Operating Instructions, 10/2016, C79000-G8976-C311-02