Toshiba TOSVERT VF-AS3 Instruction Manual page 327

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Title
Parameter name
F440
Power running torque
limit input select 1
F442
Regenerative torque limit
input select 1
Set the torque limit values for the power running and regenerative torques at <F441: Power
running torque limit level 1> and <F443: Regenerative torque limit level 1>.
Set limit treatment of the constant output zone (weak magnetic field) at <F454: Torque limit in
field weakening>. You can select either constant output limit <F454> = "0" (default setting) or
constant torque limit <F454> ="1".
Title
Parameter name
F441
Power running torque
limit level 1
F443
Regenerative torque limit
level 1
F454
Torque limit in field
weakening
You can set four patterns each for the power running torque limit or the regenerative torque
limit at the parameter settings.
Title
Parameter name
F444
Power running torque
limit level 2
F445
Regenerative torque limit
level 2
F446
Power running torque
limit level 3
F447
Regenerative torque limit
level 3
F448
Power running torque
limit level 4
F449
Regenerative torque limit
level 4
Patterns 1 to 4 can be switched by turning the input terminal ON/OFF.
Adjustment range
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F441
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11: -
12: F443
Adjustment range
0.0-249.9
250.0: Disabled
0.0-249.9
250.0: Disabled
0: Constant power limit
1: Constant torque limit
Adjustment range
0.0-249.9
250.0: Disabled
6-99
E6582062
Default setting
12
12
Unit
Default setting
%
250.0
%
250.0
0
Unit
Default setting
%
250.0
%
250.0
%
250.0
%
250.0
%
250.0
%
250.0
6. [Advanced] How to use parameters
3
4
6
9