LG PQNFB17C1 Installation And User Manual page 162

V-net acs
Table of Contents

Advertisement

Functional Specifications ACP BACnet
150
Lock (Setting)
Point number: 3
Object name: LockCommand_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Output
Meaning: This object is used to set the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)
Lock (Status)
Point number: 4
Object name: LockStatus_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)
Filter Sign
Point number: 5
Object name: FilterSign_XXX (XXX: Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the status of the filters for vent.
Present_Value property:
ACTIVE: Filter sign information is turned ON.
INACTIVE: Filter sign information is OFF.
Remarks: This object supports the Intrinsic Reporting function. When the Present_Value
property changes, the corresponding Event will be transmitted if the Event has
been registered.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acp bacnetPqnfb17c0

Table of Contents