14.2.4 GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: SIEMENS
• Controller Type: Set either of the following.
S7-300/400
S7-200
• I/F: Interface to be used
• Driver: Set either of the following.
When connecting to SIEMENS S7-300/400:
SIEMENS S7-300/400
When connecting to SIEMENS S7-200:
SIEMENS S7-200
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
14.2.4 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
14 - 6
14. CONNECTION TO SIEMENS PLC
14.2 Serial Connection
3.
4.
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
(1) SIEMENS S7-300/400
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
*2
Speed
equipment.
(Default: 38400bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bit)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: Odd)
Specify the adapter address (station
No. of the adapter to which the GOT
Adapter
is connected) in the connected
*1*2
Address
network.
(Default: 1)
Specify the host address (station No.
of the PLC that the GOT will monitor)
*1*2
Host Address
in the connected network.
(Default: 2)
*1
Set the address without overlapping the address of other
units.
*2
The GOT automatically sets the values of Transmission
Speed, Adapter Address, and Host Address to the HMI
Adapter.
Description
Range
9600bps,
19200bps,
38400bps
8bit (fixed)
1bit (fixed)
Odd (fixed)
1 to 31
1 to 31