Toshiba TOSVERT VF-AS3 Instruction Manual page 27

Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Use the PG pulse input
for frequency reference ?
YES
The polarity of PG
pulse input is positive ?
YES
Set [F376]= "6"
(4)
PG option disconnection detection [F377] = "1": in case PG option is not connected, or PG at
least one pulse is missed, "E-12" trip occurs.
It is necessary to reset the inverter power to enable the changes.
3. 2. 2
Monitoring method of pulse input command
The pulse input command frequency can be monitored.
In order to monitor the pulse input command frequency, set up the monitor display in the frequency
command value [Unit: Hz/free unit].
The pulse input command frequency can be confirmed even before the motor is used.
Initial value can be confirmed for the combination testing.
For setting method of the condition monitor, refer to the inverter instruction manual in the "monitoring
operation condition" section.
Use the PG pulse input
for frequency feedback ?
NO
Set [F376]= "1"
Set [F376]= "16"
3-9
NO
YES
Set [F376]= "0
or "11"
(PG pulse input is
not available)"
3. Functional Description
E6582148
NO
3
9
10