In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 ... 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
If a supplementary electronics with an additional current output is
implemented in the instrument, you can adjust the additional current
output separately.
In menu item"Current output 2" you specify which measured value
the additional current output refers to.
The additional current output cannot be used as an output in the
sense of a safety-instrumented application (SIL).
The procedure corresponds to the previous settings of the standard
current output. See "Setup - Current output".
Since the HART variables are very extensive, the indication was
divided into two menu items.
SITRANS LG250 - Operating Instructions