3 Functions
Example:
3.11

PID controller (technological controller)

Parameter range:
Warnings
Faults
Function chart number:
Features:
- cycle time:
MICROMASTER has an integrated technological controller (PID controller, enabled
via P2200). This can be used to process basic higher-level closed-loop control
functions. These typically include:
Closed-loop pressure control for extruders
Closed-loop water level control for pump drives
Closed-loop temperature control for fan drives
Closed-loop dancer roll position control for winder applications
And similar control tasks
The technological setpoints and actual values can be entered via the PID
motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs
(ADC, ADC2) or via serial interfaces (USS on BOP link, USS on COM link, CB on
COM link) (refer to the example). The appropriate parameterization of the BICO
parameter defines which setpoints or actual values are to be used (refer to Fig.
3-40).
PID
MOP
ADC
PID
FF
USS
BOP link
USS
COM link
CB
COM link
ADC2
Fig. 3-40
118
Command source via "USS on BOP link" interface
a) Standard method
b) BICO method
P2200
P2201 – P2355
-
-
FP3300, FP3400, FP5100
8 ms
P2254
PID
PID
P2253
SUM
RFG
PID
P2264
PT1
P2200
Structure of the technological controller (PID controller)
P0700 = 4
P1055 = 2032.8
P1056 = 2032.9
::::
(refer to P0700 for a complete list)
PID
PID
PT1
PID
Output
PID
PID
SCL
MICROMASTER 440
Issue 10/03
0
Motor
control
1
&
P2251
Operating Instructions