Applications of the F-I/O module

5.2 Application 1: Safety mode SIL3/Cat.3/PLd

5.2
Application 1: Safety mode SIL3/Cat.3/PLd
Wiring
The wiring is carried out on the front connector of the module. Refer to the "Wiring" section in
the S7-1500 Automation System
(http://support.automation.siemens.com/WW/view/en/59191792) system manual.
Sensor supply
The sensor supply can be powered internally or externally.
Wiring diagram – connecting one sensor via one channel
One sensor is connected via one channel (1oo1 evaluation) for each process signal.
The assignment of the input to an internal sensor supply of the module must take place
according to the parameter assignment "Supplied channels" (see section Supplied channels
(Page 21)).
You can also supply the sensor by means of an external sensor supply.