Codes for measuring types
The following table lists all measuring types of the analog input module along with their
codes. Enter these codes in byte 2 of the respective data record.
Table B- 2
Measurement type
Deactivated
Voltage
Current 4-wire transducer
Current 2-wire transducer
Codes for measuring ranges
The following table lists all measuring ranges of the analog input module along with their
codes. Enter these codes in byte 3 of the respective data record.
Table B- 3
Measuring range
Voltage
±2.5 V
±5 V
±10 V
1 V to 5 V
Current 4-wire transducer
0 mA to 20 mA
4 mA to 20 mA
±20 mA
Current 2-wire transducer
4 mA to 20 mA
58
Code for the measuring type
Code for the measuring range
Code
0000 0000
0000 0001
0000 0010
0000 0011
Code
0000 0111
0000 1000
0000 1001
0000 1010
0000 0010
0000 0011
0000 0100
0000 0011