(Continued)
Error code
Failure code
0028
0054
0055
0056
0022
002F
*
0029
002D
*
0032
0033
0034
0035
0037
13
003A
0057
0040
0045
* This marking trips can be selected valid or invalid by parameters.
Problem
The motor parameter , , ,
Auto-tuning error
, are not set correctly.
The motor with the capacity of 2 classes
or less than the inverter is used.
The output cable is too thin.
The inverter is used for loads other than
those of three-phase induction motors.
The motor is not connected.
The motor is rotating.
Parameter pt=6 is set and High speed
motor is connected.
Ground fault
A ground fault occurs in the output cable
or the motor.
Overcurrent of dynamic braking resistor
When inverters are fed by AC power
supply and connected with common DC
bus link, unnecessary trip occurs.
Step-out (for PM
The motor shaft is locked.
motor drive only)
One output phase is open.
An impact load is applied.
Using the DC braking function.
Inverter type error
It may be a breakdown failure.
Over speed fault
The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage
limit operation.
The input signal from VIC is equal to or
Analog input break
detection fault
less than the setting.
CPU communications
A communications error occurs between
error
control CPUs.
Over torque boost
The automatic torque boost parameter
fault
setting is too high.
The motor has too small impedance.
CPU fault 2
The control CPU is defective.
Optional unit fault 2
An optional device is defective.
CPU fault 3
The control CPU is defective.
Internal circuit fault
Internal circuit is defective.
PTC fault
PTC thermal protection is occurred.
Servo lock fault
The motor shaft is not locked in servo lock
operation.
Possible causes
Set the left column parameters correctly
Set parameter f416 to smaller 70% of
Set the left column parameters correctly
Then set f400=1, when trip occurs.
Connect the motor.
Check whether the secondary magnetic
Make an auto-tuning again after the
Choose the higher power range drive.
Check the cable and the motor for ground
Increase the deceleration time dec.
Set the supply voltage correction f307
Set the parameter f614 to 0
Unlock the motor shaft.
Check the interconnect cables between
Prolong the acceleration / deceleration
Turn off the Step-out function when using
Contact your Toshiba distributor.
Check the input voltage.
Install an optional dynamic braking
Check the VIC signal cable for breaks.
Contact your Toshiba distributor.
Set a lower automatic torque boost
Make an auto-tuning.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Contact your Toshiba distributor.
Check the PTC in motor.
Reduce the load in servo lock operation.
M-4
E6581611
Remedies
as a motor name plate and make an auto-
tuning again.
the present value, and execute the auto-
tuning again.
as a motor name plate and make an auto-
tuning again.
contactor.
rotation of the motor stops.
(1 class up drive is recommended.)
faults.
to 1 or 3.
"Disabled".
the inverter and the motor.
time.
the DC braking function or change the DC
braking to Servo lock function.
resistor. (optional)
Also, check the input signal value or
setting of .
parameter setting.
(Continued overleaf)