Siemens SIPROTEC 7RW80 Manual

Siemens SIPROTEC 7RW80 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7RW80:
Table of Contents

Advertisement

SIPROTEC
Voltage and Frequency
Protection
7RW80
V4.6
Manual
C53000-G1140-C233-1
Preface
Contents
Introduction
Functions
Mounting and Commissioning
Technical Data
Appendix
Literature
Glossary
Index
1
2
3
4
A

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7RW80

  • Page 1 Preface Contents Introduction SIPROTEC Functions Voltage and Frequency Mounting and Commissioning Protection 7RW80 Technical Data Appendix V4.6 Literature Manual Glossary Index C53000-G1140-C233-1...
  • Page 2 SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks Document version V04.00.02 of Siemens AG. Other designations in this manual might be trade- marks whose use by third parties for their own purposes would in- Release date 10.2010 fringe the rights of the owner.
  • Page 3: Functions 3

    Council Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage Directive 2006/95 EC). This conformity is proved by tests conducted by Siemens AG in accordance with the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for EMC directive, and with the standard EN 60255-27 for the low-voltage directive.
  • Page 4: Technical Data

    Additional Support Should further information on the System SIPROTEC 4 be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens rep- resentative. Our Customer Support Center provides a 24-hour service.
  • Page 5 Preface Safety Information This manual does not constitute a complete index of all required safety measures for operation of the equip- ment (module, device), as special operational conditions may require additional measures. However, it com- prises important information that should be noted for purposes of personal safety as well as avoiding material damage.
  • Page 6 The operational equipment (device, module) may only be used for such applications as set out in the catalogue and the technical description, and only in combination with third-party equipment recommended or approved by Siemens. The successful and safe operation of the device is dependent on proper handling, storage, installation, opera- tion, and maintenance.
  • Page 7 Preface Typographic and Symbol Conventions The following text formats are used when literal information from the device or to the device appear in the text flow: Parameter Names Designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are marked in bold letters in monospace type style.
  • Page 8 Preface Besides these, graphical symbols are used according to IEC 60617-12 and IEC 60617-13 or symbols derived from these standards. Some of the most frequently used are listed below: Input signal of analog quantity AND-gate operation of input values OR-gate operation of input values Exklusive OR-gate (antivalence): output is active, if only one of the inputs is active Coincidence gate (equivalence): output is active, if both inputs are...
  • Page 9: Table Of Contents

    Contents Introduction................15 Overall Operation.
  • Page 10 Contents Voltage Protection 27, 59 ............40 2.2.1 Measurement Principle .
  • Page 11 Contents SYNCHROCHECK 25 ............. .89 2.7.1 General .
  • Page 12 Contents 2.12 Auxiliary Functions ............. . . 115 2.12.1 Message Processing .
  • Page 13 Contents Mounting and Commissioning .............139 Mounting and Connections .
  • Page 14 Contents Jump of Voltage Vector ............195 User-defined Functions (CFC) .
  • Page 15: Introduction

    Introduction Overall Operation Application Scope Characteristics SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 16: Overall Operation

    1.1 Overall Operation Overall Operation The Voltage and Frequency protection SIPROTEC 7RW80 is equipped with a high performance microproces- sor. This provides numerical processing of all functions in the device, from the acquisition of the measured values up to the output of commands to the circuit breakers. Figure shows the basic structure of the device 7RW80.
  • Page 17 Introduction 1.1 Overall Operation Microcomputer System Apart from processing the measured values, the microcomputer system (μC) also executes the actual protec- tion and control functions. They especially include: • Filtering and preparation of the measured quantities • Continuous monitoring of the measured quantities •...
  • Page 18: Application Scope

    Introduction 1.2 Application Scope Application Scope The digital voltage and frequency protection SIPROTEC 4 7RW80 is a versatile device designed for protection, control, and monitoring of transformers, electrical machines and distribution systems. The device can be used for • System decoupling or for load shedding if ever there is a risk of a system collapse as a result of inadmissibly large frequency drops •...
  • Page 19 Introduction 1.2 Application Scope Communication The following interfaces are available for communication with external operating, control and memory systems. The USB DIGSI interface on the front cover serves for local communication with a PC. By means of the SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this operator interface, such as specifying and modifying configuration parameters and settings, configuring user-specific logic functions, retrieving operational messages and measured values, inquiring device conditions and mea- sured values, issuing control commands.
  • Page 20: Characteristics

    Introduction 1.3 Characteristics Characteristics General Characteristics • Powerful 32-bit microprocessor system. • Complete digital processing and control of measured values, from the sampling of the analog input quanti- ties to the initiation of outputs, for example, tripping or closing circuit breakers or other switchgear devices. •...
  • Page 21 Introduction 1.3 Characteristics Load Restoration • 4 separately adjustable load restoration stages • Individually assignable low frequency stages, which start the load restoration stage (1 to 4 for each load restoration stage) • Settable dropout ratio for all stages of the load restoration •...
  • Page 22 Introduction 1.3 Characteristics Phase Rotation • Selectable ABC or ACB by setting (static) or binary input (dynamic). User Defined Functions • Internal and external signals can be logically combined to establish user-defined logic functions • All common Boolean operations are available for programming (AND, OR, NOT, Exclusive OR, etc.) •...
  • Page 23: Functions

    Functions This chapter describes the numerous functions available on the SIPROTEC 4 device 7RW80. It shows the setting possibilities for each function in maximum configuration. Information with regard to the determination of setting values as well as formulas, if required, are also provided. Based on the following information, it can also be determined which of the provided functions should be used.
  • Page 24: General

    Functions 2.1 General General The settings associated with the various device functions may be modified using the operating or service inter- face in DIGSI in conjunction with a personal computer. Some parameters may also be changed using the con- trols on the front panel of the device. The procedure is set out in detail in the SIPROTEC System Description ./1/ 2.1.1 Functional Scope The 7RW80 relay comprises protection functions and additional functions.
  • Page 25: Setting Notes

    Functions 2.1 General 2.1.1.2 Setting Notes Setting the Functional Scope Your protection device is configured using the DIGSI software. Connect your personal computer either to the USB port on the device front or to port A or port B on the bottom side of the device depending on the device version (ordering code).
  • Page 26: Settings

    Functions 2.1 General 2.1.1.3 Settings Addr. Parameter Setting Options Default Setting Comments Grp Chge OPTION Disabled Disabled Setting Group Change Option Enabled OSC. FAULT REC. Disabled Enabled Oscillographic Fault Records Enabled 24 V/f Disabled Disabled 24 Overexcit. Protection Enabled (Volt/Hertz) VECTOR JUMP Disabled Disabled...
  • Page 27: Device, General Settings

    Functions 2.1 General 2.1.2 Device, General Settings The device requires some general information. This may be, for example, the type of annunciation to be issued in the event of an occurrence of a power system fault. 2.1.2.1 Description Command-dependent Messages "No Trip – No Flag" The indication of messages masked to local LEDs and the generation of additional messages can be made dependent on whether the device has issued a trip signal.
  • Page 28: Setting Notes

    Functions 2.1 General 2.1.2.2 Setting Notes Fault Display A new pickup by a protection element generally turns off any previously lit LEDs so that only the latest fault is displayed at any one time. It can be selected whether the stored LED displays and the spontaneous fault indi- cations on the display appear upon the new pickup, or only after a new trip signal is issued.
  • Page 29 Functions 2.1 General Information Type of In- Comments formation >Test mode >Test mode >DataStop >Stop data transmission Device OK Device is Operational and Protecting ProtActive IntSP At Least 1 Protection Funct. is Active Reset Device Reset Device Initial Start Initial Start of Device Resume Resume Clock SyncError...
  • Page 30: Power System Data 1

    Functions 2.1 General 2.1.3 Power System Data 1 2.1.3.1 Description The device requires certain data regarding the network and substation so that it can adapt its functions to this data depending on the application. This may be, for instance, nominal data of the substation and measuring transformers, polarity and connection of the measured quantities, breaker properties (where applicable), etc.
  • Page 31 Functions 2.1 General The settings Vab, Vbc or Vab, Vbc, Vx or Vab, Vbc, VSyn or Vph-g, VSyn do not allow determining the zero sequence voltage. The associated protection functions are inactive in this case. The table gives an overview of the functions that can be activated for the corresponding connection type (de- pends also on the ordering number).
  • Page 32 Functions 2.1 General Trip and Close Command Duration (Breaker) In address 210 the minimum trip command duration TMin TRIP CMD is set. This setting applies to all protec- tion functions that can initiate tripping. In address 211 the maximum close command duration TMax CLOSE CMD is set. It applies to the integrated reclosing function.
  • Page 33: Settings

    Functions 2.1 General 2.1.3.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Setting Options Default Setting Comments Vnom PRIMARY 0.10 .. 800.00 kV 20.00 kV Rated Primary Voltage Vnom SECONDARY 34 ..
  • Page 34: Information List

    Functions 2.1 General Addr. Parameter Setting Options Default Setting Comments 614A OP. QUANTITY 59 Vphph Vphph Opera. Quantity for 59 Overvolt. Vph-n Prot. 615A OP. QUANTITY 27 Opera. Quantity for 27 Undervolt. Vphph Prot. Vph-n 2.1.3.4 Information List Information Type of In- Comments formation 5145...
  • Page 35: Setting Notes

    Functions 2.1 General Depending on the selected type of connection of the voltage transformers (address 213 VT Connect. 3ph), the following measured values are recorded in the fault record: Voltage connection Van, Vbn, Vcn Vab, Vbc, VGnd Vab, Vbc Vab, Vbc, Vx Vab, Vbc, VSyn Vph-g, VSyn Note...
  • Page 36: Settings

    Functions 2.1 General 2.1.4.3 Settings Addr. Parameter Setting Options Default Setting Comments WAVEFORMTRIGGE Save w. Pickup Save w. Pickup Waveform Capture Save w. TRIP Start w. TRIP WAVEFORM DATA Fault event Fault event Scope of Waveform Data Pow.Sys.Flt. MAX. LENGTH 0.30 ..
  • Page 37: Setting Notes

    Functions 2.1 General 2.1.5.2 Setting Notes General If setting group change option is not required, Group A is the default selection. Then, the rest of this section is not applicable. If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled (address 103) when the function extent is configured.
  • Page 38: Power System Data 2

    Functions 2.1 General 2.1.6 Power System Data 2 Applications • If the primary reference current of the protected object are set, the device is able to calculate and output the percentage operational measured values. 2.1.6.1 Description The general protection data (P.System Data 2) includes parameters common to all functions, i.e. not asso- ciated with a specific protection or monitoring function.
  • Page 39: En100-Module

    Functions 2.1 General 2.1.7 EN100-Module 2.1.7.1 Functional Description The EN100-Module enables integration of the 7RW80 in 100-Mbit communication networks in control and au- tomation systems with the protocols according to IEC 61850 standard. This standard permits uniform commu- nication of the devices without gateways and protocol converters. Even when installed in heterogeneous envi- ronments, SIPROTEC 4 relays therefore provide for open and interoperable operation.
  • Page 40: Voltage Protection 27, 59

    Functions 2.2 Voltage Protection 27, 59 Voltage Protection 27, 59 Voltage protection has the task to protect electrical equipment against undervoltage and overvoltage. Both op- erational states are abnormal as overvoltage may cause for example insulation problems or undervoltage may cause stability problems.
  • Page 41: Overvoltage Protection 59

    Functions 2.2 Voltage Protection 27, 59 2.2.2 Overvoltage Protection 59 Function The overvoltage protection includes three elements (59-1 PICKUP, 59-2 PICKUP, 59 Vp>). In case of a high overvoltage, the switchoff is performed with a short-time delay, whereas in case of lower overvoltages, the switchoff is performed with a longer time delay.
  • Page 42 Functions 2.2 Voltage Protection 27, 59 Figure 2-2 Logic diagram of the overvoltage protection SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 43: Undervoltage Protection 27

    Functions 2.2 Voltage Protection 27, 59 2.2.3 Undervoltage Protection 27 Undervoltage protection consists of three elements (27-1 PICKUP, 27-2 PICKUP, 27 Vp<). Therefore, trip- ping can be time-graded depending on how severe voltage collapses are. Voltage thresholds and time delays can be set individually for both elements 27-1 PICKUP and 27-2 PICKUP.
  • Page 44 Functions 2.2 Voltage Protection 27, 59 Figure 2-4 Logic diagram of the undervoltage protection SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 45: Setting Notes

    Functions 2.2 Voltage Protection 27, 59 2.2.4 Setting Notes General Voltage protection is only in effect and accessible if address 150 27/59 is set to Enabled during configuration of protective functions. If the function is not required Disabled is set. The voltage to be evaluated is selected in Power System Data 1 (see Chapter 2.2, Table 2-2).
  • Page 46 Functions 2.2 Voltage Protection 27, 59 Overvoltage Protection - Negative Sequence System V2 In a three-phase transformer connection, parameter 614 OP. QUANTITY 59 can determine that the negative sequence system V2 can be evaluated as a measured value for the overvoltage protection. The negative se- quence system detects voltage asymmetries.
  • Page 47 Functions 2.2 Voltage Protection 27, 59 Undervoltage Protection with Phase-to-phase or Phase-to-ground Voltages For undervoltage protection with phase-to-phase or phase-to-ground voltages you have to configure at address 5109 27 Phasesthe measured quantity that is to be evaluated for the undervoltage protection. While being configured All phases all voltages have to underrun their threshold.
  • Page 48: Settings

    Functions 2.2 Voltage Protection 27, 59 2.2.5 Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Setting Options Default Setting Comments 5001 FCT 59 59 Overvoltage Protection Alarm Only 5002 59-1 PICKUP 20 ..
  • Page 49: Information List

    Functions 2.2 Voltage Protection 27, 59 Addr. Parameter Setting Options Default Setting Comments 5131 27 Vp< 10 .. 120 V 45 V 27 Pickup Vp< 5132 27 T Vp< 0.1 .. 5.0 sec 1.0 sec 27 T Vp< Time Delay 5133 Pickup - Time 0.05 ..
  • Page 50: Frequency Protection 81 O/U

    Functions 2.3 Frequency Protection 81 O/U Frequency Protection 81 O/U The frequency protection function detects abnormally high and low frequencies in the system or in electrical machines. If the frequency lies outside the allowable range, appropriate actions are initiated, such as load shedding or separating a generator from the system.
  • Page 51 Functions 2.3 Frequency Protection 81 O/U Figure 2-5 Logic diagram of the frequency protection SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 52: Setting Notes

    Functions 2.3 Frequency Protection 81 O/U 2.3.2 Setting Notes General Frequency protection is only in effect and accessible if address 154 81 O/U is set to Enabled during config- uration of protective functions. If the fuction is not required Disabled is set. The function can be turned ON or OFF under address 5401 FCT 81 O/U.
  • Page 53: Settings

    Functions 2.3 Frequency Protection 81 O/U 2.3.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Setting Options Default Setting Comments 5401 FCT 81 O/U 81 Over/Under Frequency Protec- tion 5402 Vmin 10 ..
  • Page 54: Information List

    Functions 2.3 Frequency Protection 81 O/U 2.3.4 Information List Information Type of In- Comments formation 5203 >BLOCK 81O/U >BLOCK 81O/U 5206 >BLOCK 81-1 >BLOCK 81-1 5207 >BLOCK 81-2 >BLOCK 81-2 5208 >BLOCK 81-3 >BLOCK 81-3 5209 >BLOCK 81-4 >BLOCK 81-4 5211 81 OFF 81 OFF...
  • Page 55: Load Restoration

    Functions 2.4 Load Restoration Load Restoration The Load Restoration has the task to reconnect elements of the system automatically, which have been dis- connected due to overload. Overload causes the network frequency to drop, which is detected by the under- frequency protection and leads to separation of system components.
  • Page 56 Functions 2.4 Load Restoration Figure 2-6 Load Restoration - Overview SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 57 Functions 2.4 Load Restoration Procedure The start of a load restoration element is triggered by the tripping of the associated underfrequency element. Processing will terminate, if the restoration signal for the circuit breaker is issued or the function has been blocked.
  • Page 58 Functions 2.4 Load Restoration You can adjust the trip- and dropout time for every load restoration element. Furthermore, you can adjust the pickup- and dropout time as a difference to the starting frequency, which together form the threshold of the load restoration.
  • Page 59 Functions 2.4 Load Restoration Figure 2-9 Load Restoration - Blocking and Monitoring After the monitoring time of the restoration cycle has elapsed, the success of the load restoration will be eval- uated. Success basically depends on the following criteria: • The load restoration is not blocked, e.g. by another protective function, binary input, undervoltage, monitor- •...
  • Page 60 Functions 2.4 Load Restoration Figure 2-10 Load Restoration – Blocking and Monitoring, Example SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 61: Setting Notes

    Functions 2.4 Load Restoration 2.4.2 Setting Notes General The load restoration is active, if Load Restore = Enabled has been set at address 155 during configuration. If the function is not required Disabled is set. The various elements of the load restoration are configured ON orr OFF at addresses 5520, 5540, 5560 and 5580.
  • Page 62 Functions 2.4 Load Restoration Figure 2-11 Example for Load Restoration with 3 elements In the above example the frequency initially drops below the pickup threshold of the underfrequency element 81-1. The element 81-1 trips. Because of the configured settings (see Table 2-3) load restoration element LR1 is started with the tripping of 81-1.
  • Page 63 Functions 2.4 Load Restoration During the pickup time of LR2 the network frequency drops briefly below the pickup threshold, but not below the dropout threshold of LR2. This stops the pickup of load restoration element LR2, but does not reset this procedure in the dropout delay time.
  • Page 64: Settings

    Functions 2.4 Load Restoration 2.4.3 Settings Addr. Parameter Setting Options Default Setting Comments 5501 LR t Monitor 1 .. 3600 sec 3600 sec Load restoration monitor time 5502 LR Max. Cycles 1 .. 10 Load restoration maximal no. of cycles 5520 Load restoration element 1 5521...
  • Page 65 Functions 2.4 Load Restoration Addr. Parameter Setting Options Default Setting Comments 5548 LR2 after 81-1 Load restoration element 2 after 81-1 5549 LR2 after 81-2 Load restoration element 2 after 81-2 5550 LR2 after 81-3 Load restoration element 2 after 81-3 5551 LR2 after 81-4...
  • Page 66: Information List

    Functions 2.4 Load Restoration Addr. Parameter Setting Options Default Setting Comments 5587 LR4 t CB Close 0.01 .. 32.00 sec; 0 1.00 sec Load restoration element 4 CB Close time 5588 LR4 after 81-1 Load restoration element 4 after 81-1 5589 LR4 after 81-2 Load restoration element 4 after...
  • Page 67 Functions 2.4 Load Restoration Information Type of In- Comments formation 17364 LR4 Active Load restoration element 4 Active 17365 LR4 Set-Error Load restoration element 4 Setting Error 17366 LR4 Monitor Load restoration element 4 monitor mode SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 68: Monitoring Functions

    Functions 2.5 Monitoring Functions Monitoring Functions The device is equipped with extensive monitoring capabilities - both for hardware and software. In addition, the measured values are also constantly monitored for plausibility, therefore, the voltage transformer circuits are largely covered by the integrated monitoring functions. 2.5.1 Measurement Supervision 2.5.1.1 General...
  • Page 69: Software Monitoring

    Functions 2.5 Monitoring Functions AD Transformer Monitoring The digitized sampled values are being monitored in respect of their plausibility. If the result is not plausible, message 181 „Error A/D-conv.“ is issued. The protection is blocked, thus preventing unwanted operation. Furthermore, a fault record is generated for recording of the internal fault. 2.5.1.3 Software Monitoring Watchdog For continuous monitoring of the program sequences, a time monitor is provided in the hardware (hardware...
  • Page 70 Functions 2.5 Monitoring Functions Figure 2-13 Voltage symmetry monitoring Phase sequence of the voltages To detect swapped phase connections in the voltage input circuits, the direction of rotation of the phase-to- phase voltages is checked. Therefore the sequence of the zero crossings of the currents (having the same sign) is checked.
  • Page 71: Broken Wire Monitoring Of Voltage Transformer Circuits

    Functions 2.5 Monitoring Functions 2.5.1.5 Broken Wire Monitoring of Voltage Transformer Circuits Requirements The measurement of all three phase-to-ground voltages is a requirement for the functionality. If only two phase- to-phase voltages were measured, it would not be possible to evaluate two of the required criteria. Task The „Broken Wire“...
  • Page 72: Setting Notes

    Functions 2.5 Monitoring Functions 2.5.1.6 Setting Notes Measured Value Monitoring The sensitivity of the measured value monitor can be modified. Default values are set at the factory, which are sufficient in most cases. If especially high operating asymmetry in the voltages is to be expected for the appli- cation, or if it becomes apparent during operation that certain monitoring functions activate sporadically, then the setting should be less sensitive.
  • Page 73: Trip Circuit Supervision 74Tc

    Functions 2.5 Monitoring Functions 2.5.2 Trip Circuit Supervision 74TC Devices 7RW80 are equipped with an integrated trip circuit supervision. Depending on the number of available binary inputs (not connected to a common potential), supervision with one or two binary inputs can be selected. If the allocation of the required binary inputs does not match the selected supervision type, then a message to this effect is generated („74TC ProgFail“).
  • Page 74 Functions 2.5 Monitoring Functions Supervision with two binary inputs not only detects interruptions in the trip circuit and loss of control voltage, it also supervises the response of the circuit breaker using the position of the circuit breaker auxiliary contacts. Depending on the conditions of the trip contact and the circuit breaker, the binary inputs are activated (logical condition "H"...
  • Page 75 Functions 2.5 Monitoring Functions Figure 2-17 Trip circuit supervision with one binary input During normal operation, the binary input is activated (logical condition "H") when the trip contact is open and the trip circuit is intact, because the monitoring circuit is closed by either the 52a circuit breaker auxiliary contact (if the circuit breaker is closed) or through the bypass resistor R by the 52b circuit breaker auxiliary contact.
  • Page 76: Setting Notes

    Functions 2.5 Monitoring Functions Figure 2-19 Message logic for trip circuit supervision 2.5.2.2 Setting Notes General The function is only effective and accessible if address 182 (Section 2.1.1.2) was set to either 2 Binary Inputs or 1 Binary Input during configuration, the appropriate number of binary inputs has been config- ured accordingly for this purpose and the function FCT 74TC is ON at address 8201.
  • Page 77: Settings

    Functions 2.5 Monitoring Functions 2.5.2.3 Settings Addr. Parameter Setting Options Default Setting Comments 8201 FCT 74TC 74TC TRIP Circuit Supervision 8202 Alarm Delay 1 .. 30 sec 2 sec Delay Time for alarm 2.5.2.4 Information List Information Type of In- Comments formation 6851...
  • Page 78 Functions 2.5 Monitoring Functions Table 2-5 Summary of Malfunction Responses by the Protection Relay Monitoring possible causes Malfunction Response Message (No.) Output AC/DC supply voltage loss External Device shutdown All LEDs dark drops out (auxiliary voltage) internal (converter) Buffer battery internal Message „Fail Battery“...
  • Page 79: Flexible Protection Functions

    Functions 2.6 Flexible Protection Functions Flexible Protection Functions The flexible protection function is applicable for a variety of protection principles. The user can create up to 20 flexible protection functions and configure them according to their function. Each function can be used either as an autonomous protection function, as an additional protective element of an existing protection function or as a universal logic, e.g.
  • Page 80 Functions 2.6 Flexible Protection Functions Function Blocking The function can be blocked via binary input (FNo. 235.2110 „>BLOCK $00“) or via local operating terminal („Control“ -> „Tagging“ -> „Set“). Blocking will reset the function's entire measurement logic as well as all running times and indications.
  • Page 81 Functions 2.6 Flexible Protection Functions Function Logic Figure 2-20 shows the logic diagram of a three-phase function. If the function operates on one phase or without phase reference, phase selectivity and phase-specific indications are not relevant. Figure 2-20 Logic diagram of flexible protection functions SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 82 Functions 2.6 Flexible Protection Functions The parameters can be set to monitor either exceeding or dropping below of the threshold. The configurable pickup delay time will be started once the threshold (>-element) has been exceeded. When the delay time has elapsed and the threshold is still violated, the pickup of the phase (e.g.
  • Page 83: Setting Notes

    Functions 2.6 Flexible Protection Functions 2.6.2 Setting Notes The setting of the functional scope determines the number of flexible protection functions to be used (see Chapter 2.1.1). If a flexible function in the functional scope is disabled (by removing the checkmark), this will result in losing all settings and configurations of this function or its settings will be reset to their default settings.
  • Page 84 Functions 2.6 Flexible Protection Functions Measurement Process The following table lists configurable measurement procedures depending on parameterized measured quan- tities. Table 2-8 Parameter in the Setting Dialog "Measurement Procedure", Mode of Operation 3-phase Mode of Measured Notes Operation Quantity Three-phase Voltage Parameter MEAS.
  • Page 85 Functions 2.6 Flexible Protection Functions Note With regard to the phase-selective pickup messages, a special behavior is observed in the three-phase voltage protection with phase-to-phase variables, because the phase-selective pickup message "Flx01 Pickup Lx" is allocated to the respective measured-value channel "Lx". Single-phase faults: If, for example, voltage V drops to such degree that voltages V...
  • Page 86 Functions 2.6 Flexible Protection Functions Settings The pickup thresholds, delay times and dropout ratios of the flexible protection function are set in the „Settings“ dialog box in DIGSI. The pickup threshold of the function is configured via parameter . The OFF-command delay time is set via pa- rameter T TRIP DELAY.
  • Page 87: Settings

    Functions 2.6 Flexible Protection Functions 2.6.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Setting Options Default Setting Comments FLEXIBLE FUNC. Flexible Function Alarm Only OPERRAT. MODE 3-phase 3-phase Mode of Operation 1-phase no reference...
  • Page 88: Information List

    Functions 2.6 Flexible Protection Functions Addr. Parameter Setting Options Default Setting Comments DROPOUT RATIO 0.70 .. 0.99 0.95 Dropout Ratio DROPOUT RATIO 1.01 .. 3.00 1.05 Dropout Ratio DO differential 0.02 .. 1.00 Hz 0.03 Hz Dropout differential 2.6.4 Information List Information Type of In- Comments...
  • Page 89: General

    Functions 2.7 SYNCHROCHECK 25 SYNCHROCHECK 25 When connecting two sections of a power system, the synchrocheck function verifies that the switching does not endanger the stability of the power system Applications • Typical applications are, for example, the synchronization of a feeder and a busbar or the synchronization of two busbars via tie-breaker.
  • Page 90: Synchrocheck 25

    Functions 2.7 SYNCHROCHECK 25 Figure 2-22 Cross coupling The synchrocheck function 7RW80 interacts with the control function. It is also possible to employ an external automatic reclosing system. In such a case signal exchange between the devices is accomplished via binary inputs and outputs.
  • Page 91 Functions 2.7 SYNCHROCHECK 25 Release The synchronizing function only operates if it receives a measurement request. This request may be issued by the internal control function or externally via a binary input, e.g. from an external automatic reclosing system. Before a release for closing is granted, the following conditions are checked: above the setting value Vmin but below the maximum voltage Vmax? •...
  • Page 92: De-Energized Switching

    Functions 2.7 SYNCHROCHECK 25 2.7.3 De-energized Switching Connecting two components of a power system is also possible if at least one of the components is de-ener- gized and if the measured voltage is greater than the threshold 6106 V>. With a multi-phase connection on the , all connected voltages must have a higher value than the threshold V>...
  • Page 93: Direct Command / Blocking

    Functions 2.7 SYNCHROCHECK 25 2.7.4 Direct Command / Blocking Parameter 6110 Direct CO can be set to grant a release without performing any checks. In this case, con- nection is allowed immediately when initiating the synchrocheck function. It is obviously not reasonable to combine Direct CO with other release conditions.
  • Page 94: Setting Notes

    Functions 2.7 SYNCHROCHECK 25 With External Control As another option, the synchrocheck function can be activated via external measurement requests. The syn- chrocheck function can be started via binary input using measurement request („>25 Sync requ.“ or pulse- like start and stop signals „>25 Start“, „>25 Stop“). Having completed the check, the synchrocheck func- tion issues the release message („25 CloseRelease“) (see Figure ).
  • Page 95 Functions 2.7 SYNCHROCHECK 25 General The general thresholds for the synchronizing function are set at addresses 6101 to 6112. Address 6101 Synchronizing allows you to switch the entire SYNC function group ON or OFF. If switched off, the synchrocheck does not verify the synchronization conditions and release is not granted. Parameter 6102 SyncCB is used to select the switchgear component to which the synchronization settings are applied.
  • Page 96 Functions 2.7 SYNCHROCHECK 25 Power System Data The system related data for the synchronization function are set at addresses 6121 to 6125. The parameter Balancing V1/V2 (address 6121) can be set to account for different VT ratios of the two parts of the power system (see example in Figure ).
  • Page 97 Functions 2.7 SYNCHROCHECK 25 Voltage Connections The 7RW80 provides two voltage inputs for connecting the voltage V and one voltage input for connecting the voltage V (see the following examples ). If two phase-to-phase voltages are open delta-connected to side V as reference voltage, a phase-to-phase voltage must be connected and configured for the additional voltage V to be synchronized.
  • Page 98 Functions 2.7 SYNCHROCHECK 25 If only phase-to-ground voltages are available, the reference voltage V is connected to the first voltage trans- former and the additional voltage V to the third voltage transformer. Figure 2-27 Phase-to-ground voltage connection Voltage Difference The parameters 6150 dV SYNCHK V2>V1 and 6151 dV SYNCHK V2<V1 can be set to adjust the permissible voltage differences asymmetrically.
  • Page 99: Settings

    Functions 2.7 SYNCHROCHECK 25 2.7.7 Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Setting Options Default Setting Comments 6101 Synchronizing Synchronizing Function 6102 SyncCB (Setting options depend None Synchronizable circuit breaker on configuration) 6103 Vmin...
  • Page 100: Information List

    Functions 2.7 SYNCHROCHECK 25 2.7.8 Information List Information Type of In- Comments formation 170.0001 >25-1 act >25-group 1 activate 170.0043 >25 Sync requ. >25 Synchronization request 170.0049 25 CloseRelease 25 Sync. Release of CLOSE Command 170.0050 25 Sync. Error 25 Synchronization Error 170.0051 25-1 BLOCK 25-group 1 is BLOCKED 170.2007 25 Measu.
  • Page 101 Functions 2.7 SYNCHROCHECK 25 Information Type of In- Comments formation 170.2096 25 FG-Error 25 Multiple selection of func-groups 170.2097 25 Set-Error 25 Setting error 170.2101 25-1 OFF Sync-group 1 is switched OFF 170.2102 >BLK 25 CLOSE >BLOCK 25 CLOSE command 170.2103 25 CLOSE BLK 25 CLOSE command is BLOCKED SIPROTEC, 7RW80, Manual...
  • Page 102: Overexcit. Protection (Volt/Hertz)

    Functions 2.8 Overexcit. Protection (Volt/Hertz) 24 Overexcit. Protection (Volt/Hertz) 24 Overexcitation protection is used to detect inadmissibly high induction in generators and transformers, espe- cially in power station unit transformers. The protection must intervene when the limit value for the protected object (e.g.
  • Page 103 Functions 2.8 Overexcit. Protection (Volt/Hertz) 24 The thermal characteristic is specified by 8 value pairs for overexcitation V/f (related to nominal values) and trip time t. In most cases, the specified characteristic for standard transformers provides sufficient protection. If this characteristic does not correspond to the actual thermal behavior of the object to be protected, any desired characteristic can be implemented by entering customer-specific trip times for the specified V/f overexcitation values.
  • Page 104: Setting Notes

    Functions 2.8 Overexcit. Protection (Volt/Hertz) 24 The following figure shows the logic diagram for overexcitation protection. The counter can be reset to zero by means of a blocking input or a reset input. Figure 2-29 Logic diagram of the Overecxitation protection 2.8.2 Setting Notes General...
  • Page 105 Figure 2-30 Thermal tripping time characteristic (with presettings) The characteristic of a Siemens standard transformer was selected as a default setting for the parameters 4306 to 4313. If the protection object manufacturer did not provide any information, the preset standard char- acteristic should be used.
  • Page 106: Settings

    Functions 2.8 Overexcit. Protection (Volt/Hertz) 24 Voltage Transformer Adaptation Any deviation between primary nominal voltage of the voltage transformers and of the object to be protected is compensated by an internal correction factor (V ). For this it is necessary that the relevant pa- Nom prim Nom Mach rameters 202 Vnom PRIMARY and 1101 FullScaleVolt.
  • Page 107: Jump Of Voltage Vector

    Functions 2.9 Jump of Voltage Vector Jump of Voltage Vector Consumers with their own generating plant, for example, feed power directly into a network. The incoming feeder line is usually the technical and legal ownership boundary between the network operator and these con- sumers/ producers.
  • Page 108 Functions 2.9 Jump of Voltage Vector Measuring principle For a three phase voltage connection, the vector of the positive sequence system voltage is calculated . For a single-phase connection, the connected single-phase voltage is evaluated. The phase angle change of the voltage vector is determined over a delta interval of 2 cycles.
  • Page 109: Setting Notes

    Functions 2.9 Jump of Voltage Vector Figure 2-33 Logic diagram of the vector jump detection 2.9.2 Setting Notes General The vector jump protection is only effective and available if address 146 VECTOR JUMP is set to Enabled during configuration. Under address 4601VECTOR JUMP the function can be turned ON or OFF. Pickup Values The value to be set for the vector jump (address 4602 DELTA PHI) depends on the feed and load conditions.
  • Page 110: Settings

    Functions 2.9 Jump of Voltage Vector Time Delays The time delay T DELTA PHI (address 4603) should be left at zero, unless you wish to transmit the trip indi- cation with a delay to a logic (CFC), or to leave enough time for an external blocking to take effect. After expiry of the timer T RESET (address 4604), the protection function is automatically reset.
  • Page 111: Phase Rotation

    Functions 2.10 Phase Rotation 2.10 Phase Rotation A phase rotation function via binary input and parameter is implemented in 7RW80 devices. Applications • Phase rotation ensures that all protective and monitoring functions operate correctly even with anti-clock- wise rotation, without the need for two phases to be reversed. 2.10.1 Description General...
  • Page 112: Setting Notes

    Functions 2.10 Phase Rotation 2.10.2 Setting Notes Setting the Function Parameter The normal phase sequence is set at 209 (see Section 2.1.3). If, on the system side, phase rotation is reversed temporarily, then this is communicated to the protective device using the binary input „>Reverse Rot.“ (5145).
  • Page 113: Function Logic

    Functions 2.11 Function Logic 2.11 Function Logic The function logic coordinates the execution of protection and auxiliary functions, it processes the resulting de- cisions and information received from the system. This includes in particular: – Fault Detection / Pickup Logic –...
  • Page 114: Setting Notes

    Functions 2.11 Function Logic usual – remains blocked as long as the trip signal is present, and that the trip coil current is interrupted by the auxiliary contact of the circuit breaker. Figure 2-35 Terminating the Trip Signal 2.11.3 Setting Notes Trip Signal Duration The minimum trip command duration TMin TRIP CMD was described already in Section 2.1.3.
  • Page 115: Auxiliary Functions

    Functions 2.12 Auxiliary Functions 2.12 Auxiliary Functions The general functions of the device are described in chapter Auxiliary Functions. 2.12.1 Message Processing After the occurrence of a system fault, information regarding the response of the protective relay and the mea- sured values is important for a detailed analysis.
  • Page 116: Information Via Display Field Or Pc

    Functions 2.12 Auxiliary Functions 2.12.1.2 Information via Display Field or PC Using the front PC interface or the port B at the botton, a personal computer can be connected, to which the information can be sent. The relay is equipped with several event buffers for operational messages, circuit breaker statistics, etc., which are protected against loss of the auxiliary voltage by a buffer battery.
  • Page 117: Information To A Control Center

    Functions 2.12 Auxiliary Functions Retrievable Messages The messages for the last eight network faults can be retrieved and read out. The definition of a network fault is such that the time period from fault detection up to final clearing of the disturbance is considered to be one network fault.
  • Page 118: Setting Notes

    Functions 2.12 Auxiliary Functions 2.12.2.2 Setting Notes Reading/Setting/Resetting Counters The SIPROTEC 4 System Description provides a description of how to read out the statistical counters via the device front panel or DIGSI. Setting or resetting of these statistical counters takes place under the menu item MESSAGES —>...
  • Page 119: Displaying Of Measured Values

    Functions 2.12 Auxiliary Functions 2.12.3.1 Displaying of Measured Values Table 2-10 Conversion formulae between secondary, primary and percentage values Measured Second- Primary Values Ph-N sec. A–B B–C C–A Ph-Ph sec. N sec. x sec. Frequenz f in Hz f in Hz Table 2-11 Legend for the conversion formulae Parameter...
  • Page 120: Transfer Of Measured Values

    Functions 2.12 Auxiliary Functions 2.12.3.2 Transfer of Measured Values Measured values can be transferred to a central control and storage device via port B. The measuring range in which these values are transmitted depend on the protocol and, if necessary, additional settings.
  • Page 121: Min/Max Measurement Setup

    Functions 2.12 Auxiliary Functions 2.12.4 Min/Max Measurement Setup Minimum and maximum values are calculated by the 7RW80. Time and date of the last update of the values can also be read out. 2.12.4.1 Description Minimum and Maximum Values The minimum and maximum values of the three phase-to-ground voltages V , the phase-to-phase voltages , the positive-sequence component V , the voltage V...
  • Page 122: Information List

    Functions 2.12 Auxiliary Functions 2.12.4.4 Information List Information Type of In- Comments formation ResMinMax IntSP_Ev Reset Minimum and Maximum counter >V MiMaReset >V MIN/MAX Buffer Reset >VphphMiMaRes >Vphph MIN/MAX Buffer Reset >V1 MiMa Reset >V1 MIN/MAX Buffer Reset >Frq MiMa Reset >Frq.
  • Page 123: Set Points For Measured Values

    Functions 2.12 Auxiliary Functions 2.12.5 Set Points for Measured Values SIPROTEC devices facilitate the setting of limit values for some measured and metered values. If any of these limit values is reached, exceeded or fallen below during operation, the device issues an alarm which is indicat- ed in the form of an operational message.
  • Page 124: Information List

    Functions 2.12 Auxiliary Functions 2.12.6.3 Information List Information Type of In- Comments formation OpHour> Operating hours greater than SP. Op Hours> Set Point Operating Hours 2.12.7 Energy Metering The energy values are determinated via binary input pulses. 2.12.7.1 Setting Notes Setting of parameter for meter resolution Parameter 8315 MeterResolution can be used to maximize the resolution of the metered energy values by Factor 10 or Factor 100 compared to the Standard setting.
  • Page 125: Commissíoning Aids

    Functions 2.12 Auxiliary Functions 2.12.8 Commissíoning Aids In test mode or during commissioning, the device information transmitted to a central or storage device can be influenced. There are tools available for testing the system interface (port B) and the binary inputs and outputs of the device.
  • Page 126 Functions 2.12 Auxiliary Functions Creating Oscillographic Recordings for Tests During commissioning, energization sequences should be carried out to check the stability of the protection also during closing operations. Oscillographic event recordings contain the maximum information on the be- havior of the protection. Along with the capability of storing fault recordings via pickup of the protection function, the 7RW80 also has the capability of capturing the same data when commands are given to the device via the service program DIGSI, the serial interface, or a binary input.
  • Page 127: Breaker Control

    Functions 2.13 Breaker Control 2.13 Breaker Control A control command function is integrated in the SIPROTEC 4 7RW80 to coordinate the operation of circuit breakers and other equipment in the power system. Control commands can originate from four command sources: •...
  • Page 128: Information List

    Functions 2.13 Breaker Control Operation using DIGSI Switchgear can be controlled via the operator control interface with a PC using the DIGSI software. The pro- cedure to do so is described in the SIPROTEC 4 System Description (Control of Switchgear). Operation Using the System Interface Switchgear can be controlled via the serial system interface and a connection to the substation control equip- ment.
  • Page 129: Command Types

    Functions 2.13 Breaker Control 2.13.2 Command Types In conjunction with the power system control several command types can be distinguished for the device: 2.13.2.1 Description Commands to the Process These are all commands that are directly output to the switchgear to change their process state: •...
  • Page 130: Command Sequence

    Functions 2.13 Breaker Control 2.13.3 Command Sequence Safety mechanisms in the command sequence ensure that a command can only be released after a thorough check of preset criteria has been successfully concluded. Standard Interlocking checks are provided for each individual control command. Additionally, user-defined interlocking conditions can be programmed separately for each command.
  • Page 131: Interlocking

    Functions 2.13 Breaker Control 2.13.4 Interlocking System interlocking is executed by the user-defined logic (CFC). 2.13.4.1 Description Interlocking checks in a SICAM/SIPROTEC 4 system are normally divided in the following groups: • System interlocking relies on the system data base in the substation or central control system. •...
  • Page 132 Functions 2.13 Breaker Control Figure 2-37 Example of an operational annunciation for switching circuit breaker 52 (Q0) Standard Interlocking (default) The standard interlockings contain the following fixed programmed tests for each switching device, which can be individually enabled or disabled using parameters: •...
  • Page 133 Functions 2.13 Breaker Control The "Switching authority" object serves for interlocking or enabling LOCAL control but not REMOTE or DIGSI commands. With a 7RW80, the switching authority can be changed between "REMOTE" and "LOCAL" on the operator panel after having entered the password or by means of CFC also via binary inputs and a function key. The "Switching authority DIGSI"...
  • Page 134 Functions 2.13 Breaker Control Switching Mode The switching mode serves for activating or deactivating the configured interlocking conditions at the time of the switching operation. The following switching modes (local) are defined: • For local commands (CS = LOCAL) – locked (normal) or –...
  • Page 135 Functions 2.13 Breaker Control Blocking by Protection The pickup of protective elements blocks switching operations. Protective elements are configured, separately for each switching component, to block specific switching commands sent in CLOSE and TRIP direction. When enabled, "Block CLOSE commands" blocks CLOSE commands, whereas "Block TRIP commands" blocks TRIP signals.
  • Page 136: Command Logging

    Functions 2.13 Breaker Control 2.13.5 Command Logging During the processing of the commands, independent of the further message routing and processing, command and process feedback information are sent to the message processing centre. These messages contain information on the cause. With the corresponding allocation (configuration) these messages are entered in the event list, thus serving as a report.
  • Page 137: Notes On Device Operation

    Functions 2.14 Notes on Device Operation 2.14 Notes on Device Operation The operation of the 7RW80 slightly differs from the other SIPROTEC 4 devices. These differences are de- scribed in the following. General information regarding the operation and configuration of SIPROTEC 4 devices is set out in the SIPROTEC 4 System Description.
  • Page 138 Functions 2.14 Notes on Device Operation In part, the sixth line is used for representing e.g. the active parameter group. Figure 2-39 Representation of the active parameter group (line 6) ■ SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 139: Mounting And Commissioning

    Mounting and Commissioning This chapter is intended for experienced commissioning staff. He must be familiar with the commissioning of protection and control systems, the management of power systems and the safety rules and regulations. Hard- ware adjustments to the power system data might be necessary. The primary tests require the protected object (line, transformer, etc.) to carry load.
  • Page 140: Mounting And Connections

    Mounting and Commissioning 3.1 Mounting and Connections Mounting and Connections General WARNING! Warning of improper transport, storage, installation or assembly of the device. Failure to observe these precautions can result in death, personal injury, or serious material damage. Trouble-free and safe use of this device depends on proper transport, storage, installation, and assembly of the device according to the warnings in this device manual.
  • Page 141 Mounting and Commissioning 3.1 Mounting and Connections Setting Group Change If binary inputs are used to switch setting groups, please observe the following: • Two binary inputs must be dedicated to the purpose of changing setting groups when four groups are to be switched.
  • Page 142 Mounting and Commissioning 3.1 Mounting and Connections Figure 3-2 Trip circuit supervision with one binary input This results in an upper limit for the resistance dimension, R , and a lower limit R , from which the optimal value of the arithmetic mean R should be selected: In order that the minimum voltage for controlling the binary input is ensured, R is derived as: So the circuit breaker trip coil does not remain energized in the above case, R...
  • Page 143 Mounting and Commissioning 3.1 Mounting and Connections Constant current with activated BI ( = 0.25 mA) BI (HIGH) Minimum control voltage for BI (= 19 V at delivery setting for nominal voltages of 24 BI min V/ 48 V; 88 V at delivery setting for nominal voltages of 60 V/ 110 V/ 125 V/ 220 V/ 250 V) Control voltage for trip circuit Ohmic resistance of the circuit breaker coil...
  • Page 144: Hardware Modifications

    Any service activities exceeding the installation or exchange of commu- nication modules must only be carried out by Siemens personnel. For preparing the workplace, a pad suitable for electrostatic sensitive devices (ESD) is required.
  • Page 145 Mounting and Commissioning 3.1 Mounting and Connections Note In order to minimize the expenditure for reconnecting the device, remove the completely wired terminal blocks from the device. To do so, open the elastic holders of the terminal blocks in pairs with a flat screwdriver and remove the terminal blocks to the back.
  • Page 146 Make sure that the defective fuse has not left any obvious damage on the device. If the fuse trips again after reconnection of the device, refrain from any further repairs and send the device to Siemens for repair. The device can now be reassembled again (see Section Reassembly).
  • Page 147: Connections Of The Voltage Terminals

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.2.2 Connections of the Voltage Terminals Fixing Elements The fixing elements for the voltage transformer connection are part of the voltage terminal (housing side). They have a stress-crack- and corrosion-resistant alloy. The head shape of the terminal screw allows for using a flat screwdriver (4.0 mm x 0.8 mm / 0.16 in x 0.031 in) or a crosstip screwdriver (PZ1).
  • Page 148 Mounting and Commissioning 3.1 Mounting and Connections Installation or Replacement of the Ethernet Interface Module The following requirement must be fulfilled: There is no SIPROTEC 4 communication module mounted yet. Otherwise, this has to be removed before ac- tually installing the Ethernet interface module (see below). The Ethernet interface module is inserted in the respective slot, most suitably from the open bottom, i.e.
  • Page 149 Mounting and Commissioning 3.1 Mounting and Connections Installation or Replacement of a SIPROTEC 4 Communication Module The following description assumes the normal case that a SIPROTEC 4 communication module which has not yet been existing is retrofitted. If a SIPROTEC 4 communication module has to be removed or replaced, the steps are to be performed in reverse order.
  • Page 150: Reassembly

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.2.4 Reassembly The reassembly of the device is performed in the following steps: Carefully insert the complete electronics block into the housing. Please observe the following: The connections of the communication modules point at the bottom of the housing. Insert the electronics block into the housing, until the supporting part rests against the front edge of the hous- ing.
  • Page 151: Installation

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.3 Installation 3.1.3.1 General The 7RW80 relay has a housing size 1/6. The housing has 2 covers and 4 fixing holes each at the top and bottom (see Figure 3-9 and Figure 3-10). Figure 3-9 Housing with covers Figure 3-10...
  • Page 152: Panel Flush Mounting

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.3.2 Panel Flush Mounting The housing (housing size ) has 2 covers and 4 fixing holes. • Remove the 2 covers at the top and bottom of the front cover. Thus, 4 elongated holes are revealed in the mounting bracket and can be accessed.
  • Page 153: Cubicle Mounting

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.3.3 Cubicle Mounting To install the device in a rack or cubicle, two mounting brackets are required. The ordering codes are stated in Appendix, Section A.1. The housing (housing size ) has 2 covers and 4 fixing holes. •...
  • Page 154: Panel Surface Mounting

    Mounting and Commissioning 3.1 Mounting and Connections 3.1.3.4 Panel Surface Mounting When ordering the device as surface-mounting case (9th digit of the ordering number= B), the mounting frame shown below is part of the scope of delivery. For installation, proceed as follows: •...
  • Page 155: Checking Connections

    Mounting and Commissioning 3.2 Checking Connections Checking Connections 3.2.1 Checking the Data Connections of the Interfaces Pin Assignment The following tables show the pin assignment of the various interfaces. The position of the connections can be seen in the following figures. Figure 3-14 USB interface Figure 3-15...
  • Page 156 Mounting and Commissioning 3.2 Checking Connections USB Interface The USB interface can be used to establish a connection between the protection device and your PC. For the communication, the Microsoft Windows USB driver is used which is installed together with DIGSI (as of version V4.82).
  • Page 157 Mounting and Commissioning 3.2 Checking Connections Connections at port B Table 3-4 Assignment of the port B sockets Pin No. RS232 RS485 Profibus DP, RS485 Modbus RS485 Ethernet IEC 60870–5–103 DNP3.0 RS485 EN 100 redundant Shield (electrically connected with shield shroud) B/B’...
  • Page 158: Checking The System Connections

    Mounting and Commissioning 3.2 Checking Connections 3.2.2 Checking the System Connections WARNING! Warning of dangerous voltages Non-observance of the following measures can result in death, personal injury or substantial property damage. Therefore, only qualified people who are familiar with and adhere to the safety procedures and precautionary measures should perform the inspection steps.
  • Page 159: Commissioning

    Mounting and Commissioning 3.3 Commissioning Commissioning WARNING! Warning of dangerous voltages when operating an electrical device Non-observance of the following measures can result in death, personal injury or substantial property damage. Only qualified people shall work on and around this device. They must be thoroughly familiar with all warnings and safety notices in this instruction manual as well as with the applicable safety steps, safety regulations, and precautionary measures.
  • Page 160: Test Mode And Transmission Block

    Mounting and Commissioning 3.3 Commissioning 3.3.1 Test Mode and Transmission Block Activation and Deactivation If the device is connected to a central or main computer system via the SCADA interface, then the information that is transmitted can be influenced. This is only possible with some of the protocols available (see Table „Pro- tocol-dependent functions“...
  • Page 161 Mounting and Commissioning 3.3 Commissioning Figure 3-17 Interface test with the dialog box: creating messages – example Changing the Operating State When clicking one of the buttons in the column Action for the first time, you will be prompted for the password no.
  • Page 162: Configuring Communication Modules

    Mounting and Commissioning 3.3 Commissioning 3.3.3 Configuring Communication Modules Required Settings in DIGSI 4 The following applies in general: In the case of a first-time installation or replacement of a communication module, the ordering number (MLFB) does not need to be changed. The ordering number can be retained. Thus, all previously created parameter sets remain valid for the device.
  • Page 163 Mounting and Commissioning 3.3 Commissioning Mapping File For Profibus DP, Modbus and DNP3.0, a matching bus mapping has to be selected. For the selection of the mapping file please open the SIPROTEC device in DIGSI and choose the function „In- terfaces”...
  • Page 164 Mounting and Commissioning 3.3 Commissioning Figure 3-20 Module-specific settings Then, transfer the data to the protection device (see the following figure). Figure 3-21 Transmitting data SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 165: Checking The Status Of Binary Inputs And Outputs

    Mounting and Commissioning 3.3 Commissioning Terminal Test The system interface (EN 100) is preassigned with the default value zero and the module is thus set to DHCP mode. The IP address can be set in the DIGSI Manager (Object properties... / Communication parameters / System interface [Ethernet]).
  • Page 166 Mounting and Commissioning 3.3 Commissioning Structure of the Test Dialog Box The dialog box is classified into three groups: BI for binary inputs, REL for output relays, and LED for light- emitting diodes. On the left of each of these groups is an accordingly labelled button. By double-clicking a button, information regarding the associated group can be shown or hidden.
  • Page 167 Mounting and Commissioning 3.3 Commissioning Proceed as follows in order to check the output relay : • Ensure that the switching of the output relay can be executed without danger (see above under DANGER!). • Each output relay must be tested via the corresponding Scheduled-cell in the dialog box. •...
  • Page 168: Testing User-Defined Functions

    Mounting and Commissioning 3.3 Commissioning 3.3.5 Testing User-Defined Functions CFC Logic The device has a vast capability for allowing functions to be defined by the user, especially with the CFC logic. Any special function or logic added to the device must be checked. Of course, general test procedures cannot be given.
  • Page 169: Polarity Check For Voltage Input V

    Mounting and Commissioning 3.3 Commissioning 3.3.7 Polarity Check for Voltage Input V Depending on the application of the voltage measuring input V of a 7RW80, a polarity check may be neces- sary. If no measuring voltage is connected to this input, this section is irrelevant. (Power System data 1 address 213VT If input V is used for measuring the displacement voltage V...
  • Page 170 Mounting and Commissioning 3.3 Commissioning • Close the VT mcb of the busbar voltage again. • Open the circuit breaker. • For the synchrocheck, the program SYNC V1<V2> is set to YES (address 6107) and SYNC V1>V2< is set to NO (address 6108). •...
  • Page 171: Trip/Close Tests For The Configured Operating Devices

    Mounting and Commissioning 3.3 Commissioning 3.3.8 Trip/Close Tests for the Configured Operating Devices Control by Local Command If the configured equipment was not switched sufficiently in the hardware test already described, configured equipment must be switched on and off from the device via the integrated control element. The feedback infor- mation on the circuit breaker position injected via binary inputs is to be read out at the device and compared with the actual breaker position.
  • Page 172: Creating A Test Fault Record

    Mounting and Commissioning 3.3 Commissioning 3.3.9 Creating A Test Fault Record General In order to be able to test the stability of the protection during switchon procedures also, switchon trials can also be carried out at the end. Oscillographic records obtain the maximum information about the behaviour of the protection.
  • Page 173: Final Preparation Of The Device

    Mounting and Commissioning 3.4 Final Preparation of the Device Final Preparation of the Device Firmly tighten all screws. Tighten all terminal screws, including those that are not used. Caution! Inadmissable Tightening Torques Non–observance of the following measure can result in minor personal injury or property damage. The tightening torques must not be exceeded as the threads and terminal chambers may otherwise be dam- aged! The settings should be checked again, if they were changed during the tests.
  • Page 174 Mounting and Commissioning 3.4 Final Preparation of the Device SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 175: Technical Data

    Technical Data General Device Data Voltage Protection (27, 59) Frequency Protection 81 O/U Load Restoration Flexible Protective Functions Synchrocheck 25 Overecxitation Protection 24 Jump of Voltage Vector User-defined Functions (CFC) 4.10 Additional Functions 4.11 Breaker Control 4.12 Dimensions SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 176: General Device Data

    Technical Data 4.1 General Device Data General Device Data 4.1.1 Analog Inputs Voltage Inputs Nominal frequency 50 Hz or 60 Hz (adjustable) Operating range frequency (not dependent on the nominal fre- 25 Hz to 70 Hz quency Nominal Voltage 34 V – 225 V (adjustable) for connection of phase-to-ground voltages 34 V –...
  • Page 177: Binary Inputs And Outputs

    Technical Data 4.1 General Device Data 4.1.3 Binary Inputs and Outputs Binary Inputs Variant Quantity 7RW801 3 (configurable) 7RW802 7 (configurable) DC nominal voltage range 24 V to 250 V Current Consumption (independent of the control approx. 0.4 mA voltage) Pickup time approx.
  • Page 178: Communication Interfaces

    Technical Data 4.1 General Device Data 4.1.4 Communication Interfaces Operator Interface Terminal Front side, non-isolated, USB type B socket for connecting a personal computer Operation from DIGSI V4.82 via USB 2.0 full speed Operation With DIGSI Transmission speed up to 12 Mbit/s max. Bridgeable distance Port A Ethernet electrical for DIGSI...
  • Page 179 Technical Data 4.1 General Device Data Fibre Optical Link (FO) FO connector type ST-Connector Connection Back case bottom, mounting location "B” Optical wavelength λ = 820 nm Laser Class 1 according to using glass fiber 50 μm/125 μm or using EN 60825-1/-2 glass fiber 62.5 μm/125 µm Permissible optical link signal...
  • Page 180: Electrical Tests

    Technical Data 4.1 General Device Data Ethernet electrical (EN 100) for IEC61850 and DIGSI Connection Back case bottom, mounting location "B” 2 x RJ45 socket 100BaseT in acc. with IEEE802.3 Test voltage (with regard to the 500 V; 50 Hz socket) Transmission Speed 100 Mbit/s...
  • Page 181 Technical Data 4.1 General Device Data EMC Tests for Immunity (Type Tests) Standards: IEC 60255-6 and -22, (product standards) IEC/EN 61000-6-2 VDE 0435 For more standards see also individual functions 1 MHz test, Class III IEC 60255-22-1, IEC 61000-4-18, IEEE 2.5 kV (Peak);...
  • Page 182: Mechanical Stress Tests

    Technical Data 4.1 General Device Data 4.1.6 Mechanical Stress Tests Vibration and Shock Stress during Stationary Operation Standards: IEC 60255-21 and IEC 60068 Oscillation Sinusoidal IEC 60255-21-1, Class II; 10 Hz to 60 Hz: ± 0,075 mm amplitude; 60 Hz to 150 Hz: IEC 60068-2-6 1g acceleration frequency sweep rate 1 octave/min 20 cycles in 3 orthog-...
  • Page 183: Climatic Stress Tests

    56 days of the year up to 93 % relative humidity; con- densation must be avoided! Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur.
  • Page 184: Design

    Technical Data 4.1 General Device Data 4.1.9 Design Case 7XP20 Dimensions see dimensional drawings, Section 4.12 Variant Case Size Weight (mass) 7RW80**-*B in surface mounting housing 8.8 lb or 4.5 kg 7RW80**-*E in flush mounting housing 8.8 lb or 4 kg International Protection Under IEC 60529 For surface mounting housing equipment IP 50...
  • Page 185: Voltage Protection (27, 59)

    Technical Data 4.2 Voltage Protection (27, 59) Voltage Protection (27, 59) Setting Ranges / Increments Undervoltages 27-1, 27-2, 27-Vp< (V<, V<<, Vp<) Measured quantity used - Positive sequence system of the voltages With three-phase connection: - Phase-to-phase voltage - Phase-to-ground-voltage Measured quantity used Connected single-phase phase-to-ground voltage with single-phase connection...
  • Page 186 Technical Data 4.2 Voltage Protection (27, 59) Times Pickup times - Undervoltage 27-1 (V<), 27-2 (V<<), 27-1 V <, 27-2 V <<, 27- approx. 50 ms Vp< approx. 50 ms - Overvoltage 59-1 (V>), 59-2 (V>>), 59-Vp> approx. 60 ms - Overvoltage 59-1V , 59-2V , 59-1V...
  • Page 187: Frequency Protection 81 O/U

    Technical Data 4.3 Frequency Protection 81 O/U Frequency Protection 81 O/U Setting Ranges / Increments Number of frequency elements 4; each can be set to f> or f< Pickup values f> or f< 40.00 Hz to 60.00 Hz Increments 0.01 Hz for f = 50 Hz Pickup values f>...
  • Page 188: Load Restoration

    Technical Data 4.4 Load Restoration Load Restoration Setting Ranges / Increments Number of load restoration stages Start threshold with f = 50 Hz 40.00 Hz to 60.00 Hz Increments 0.01 Hz Start threshold with f = 60 Hz 50.00 Hz to 70.00 Hz Increments 0.01 Hz Pickup Threshold 0.02 Hz to 2.00 Hz...
  • Page 189: Flexible Protective Functions

    Technical Data 4.5 Flexible Protective Functions Flexible Protective Functions Measured Quantities / Operating Modes Three-phase V, 3V , V1, V2, dV/dt, df/dt Single-phase V, V Without fixed phase reference f, binary input Measuring procedure for V Fundamental wave, True RMS value, Positive Sequence System, Negative sequence system, Zero sequence system...
  • Page 190 Technical Data 4.5 Flexible Protective Functions Times Pickup times: Voltage (phase quantities) for 2 times the setting value approx. 30 ms for 10 times the setting value approx. 20 ms Voltage (symmetrical components) for 2 times the setting value approx. 40 ms for 10 times the setting value approx.
  • Page 191: Synchrocheck 25

    Technical Data 4.6 Synchrocheck 25 Synchrocheck 25 Operating Modes - Synchrocheck Additional Release Conditions - Live bus / dead line, - Dead bus / live line, - Dead bus and dead line - Bypassing Voltages Maximum operating voltage V 20 V to 140 V (phase-to-phase) Increments 1 V Minimum operating voltage V 20 V to 125 V (phase-to-phase) Increments 1 V V<...
  • Page 192 Technical Data 4.6 Synchrocheck 25 Measured Values of the Synchrocheck Function Reference voltage V1 in kV primary, in V secondary or in % of V - Range 10 % to 120 % of V - Tolerance ≤ 1 % of measured value, or 0.5 % of V Voltage to be synchronized V2 in kV primary, in V secondary or in % of V - Range...
  • Page 193: Overecxitation Protection 24

    Technical Data 4.7 Overecxitation Protection 24 Overecxitation Protection 24 Setting Ranges / Increments Pickup threshold of the warning stage 1.00 to 1.20 Increments 0.01 Pickup threshold of the stage characteristic 1.00 to 1.40 Increments 0.01 Delay times T V/f>, T V/f>> 0.00 s to 60.00 s Increments 0.01 s (Alarm and stage characteristic)
  • Page 194 Technical Data 4.7 Overecxitation Protection 24 Figure 4-1 Resulting Tripping Characteristic from Thermal Replica and Stage Characteristic of the Over- excitation Protection (Default Setting) SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 195: Jump Of Voltage Vector

    Technical Data 4.8 Jump of Voltage Vector Jump of Voltage Vector Setting Ranges / Increments Stage Δϕ 2° to 30° Increments 1° Delay times T 0.00 to 60.00 s Increments 0.01 s or ∞ (inactive) Reset Time T 0.00 to 60.00 s Increments 0.00 s Reset or ∞...
  • Page 196: User-Defined Functions (Cfc)

    Technical Data 4.9 User-defined Functions (CFC) User-defined Functions (CFC) Function Modules and Possible Assignments to Task Levels Function Module Explanation Task Level PLC1_ PLC_ SFS_ BEARB BEARB BEARB BEARB ABSVALUE Magnitude Calculation — — — Addition ALARM Alarm clock AND - Gate FLASH Blink block BOOL_TO_CO...
  • Page 197 Technical Data 4.9 User-defined Functions (CFC) Function Module Explanation Task Level PLC1_ PLC_ SFS_ BEARB BEARB BEARB BEARB Multiplication MV_GET_STATUS Decode status of a value MV_SET_STATUS Set status of a value NAND NAND - Gate Negator NOR - Gate OR - Gate REAL_TO_DINT Adaptor REAL_TO_INT...
  • Page 198 Technical Data 4.9 User-defined Functions (CFC) Device-specific Limits Designation Limit Comment Maximum number of synchronous When the limit is exceeded, an error message is output by changes of chart inputs per task level the device. Consequently, the device starts monitoring. The red ERROR-LED lights up.
  • Page 199 Technical Data 4.9 User-defined Functions (CFC) Processing Times in TICKS Required by the Individual Elements Individual Element Number of TICKS Block, basic requirement Each input more than 3 inputs for generic modules Connection to an input signal Connection to an output signal Additional for each chart Arithmetic ABS_VALUE...
  • Page 200 Technical Data 4.9 User-defined Functions (CFC) Individual Element Number of TICKS Type converter BOOL_TO_DI BUILD_DI DI_TO_BOOL DM_DECODE DINT_TO_REAL DIST_DECODE UINT_TO_REAL REAL_TO_DINT REAL_TO_UINT Comparison COMPARE LOWER_SETPOINT UPPER_SETPOINT LIVE_ZERO ZERO_POINT Metered value COUNTER Time and clock pulse TIMER TIMER_LONG TIMER_SHORT ALARM FLASH Configurable in Matrix In addition to the defined preassignments, indications and measured values can be freely configured to buff- ers, preconfigurations can be removed.
  • Page 201: Additional Functions

    Technical Data 4.10 Additional Functions 4.10 Additional Functions Operational Measured Values Voltages (phase-to-ground) in kV primary, in V secondary or in % of V Voltages (phase-to-phase) or V ph-N Positive sequence component V Negative sequence component V Range 10 % bis 120 % von V Tolerance 1,5 % vom Messwert, bzw.
  • Page 202 Technical Data 4.10 Additional Functions Local Measured Values Monitoring Voltage Asymmetry > balance factor, for V > V Voltage phase sequence Clockwise (ABC) / counter-clockwise (ACB) Fault Recording maximum of 8 fault records saved; memory maintained by buffer battery in the case of auxiliary voltage failure Recording time 5 s per fault record, in total up to 18 s at 50 Hz (max.
  • Page 203 Technical Data 4.10 Additional Functions Group Switchover of the Function Parameters Number of available setting groups 4 (parameter group A, B, C and D) Switchover can be performed via the keypad on the device DIGSI using the operator interface protocol using port B binary input IEC 61850 GOOSE (Inter-Relay Communication) The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking.
  • Page 204: Breaker Control

    Technical Data 4.11 Breaker Control 4.11 Breaker Control Number of Controlled Switching Devices Depends on the number of binary inputs and outputs available Interlocking Freely programmable interlocking Messages Feedback messages; closed, open, intermediate position Control Commands Single command / double command Switching Command to Circuit Breaker 1-, 1½...
  • Page 205: Dimensions

    Technical Data 4.12 Dimensions 4.12 Dimensions 4.12.1 Panel Flush and Cubicle Mounting (Housing Size 1/6) Figure 4-2 Dimensional drawing of a 7RW80 for Panel Fush and Cubicle Mounting (Housing Size Note For cubicle mounting a mounting bracket set (containing upper and lower mounting rails) is needed (Order No.
  • Page 206: Panel Surface Mounting (Housing Size 1/6)

    Technical Data 4.12 Dimensions 4.12.2 Panel Surface Mounting (Housing Size 1/6) Figure 4-3 Dimensional drawing of a 7RW80 for panel flush mounting (housing size 4.12.3 Bottom view Figure 4-4 Bottom view of a 7RW80 (housing size ■ SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 207: Appendix

    Appendix This appendix is primarily a reference for the experienced user. This section provides ordering information for the models of this device. Connection diagrams indicating the terminal connections of the models of this device are included. Following the general diagrams are diagrams that show the proper connections of the devices to primary equipment in many typical power system configurations.
  • Page 208: Ordering Information And Accessories

    Appendix A.1 Ordering Information and Accessories Ordering Information and Accessories A.1.1 Ordering Information A.1.1.1 7RW80 V4.6 10 11 12 13 14 15 16 Supplemen- Voltage and tary Frequency Protection – – Number of Binary Inputs and Outputs Pos. 6 Housing 1/6 19” 3x V, 3 BI, 5 BO (2 changeover contacts), 1 Life Status Contact Housing 1/6 19”...
  • Page 209 IEC 61850 100Mbit Ethernet, electrical, double, RJ45 connector + L 0 R IEC 61850 100Mbit Ethernet optical, double, LC duplex connector + L 0 S Converter Order Number SIEMENS OLM 6GK1502–2CB10 For single ring SIEMENS OLM 6GK1502–3CB10 For double ring The converter requires an operating voltage of DC 24 V.
  • Page 210 Appendix A.1 Ordering Information and Accessories Functions Pos. 15 Description ANSI No. Description Voltage and Frequency Protection 27/59 Under/Overvoltage 64/59N Displacement Voltage 81 U/O Under/Overfrequency, f< ,f> Phase Rotation 74TC Trip Circuit Supervision Lock out — Cold load pickup (dynamic setting changes) Monitoring Functions Breaker control Flexible protection functions (parameters from voltage),...
  • Page 211 Appendix A.1 Ordering Information and Accessories Functions Pos. 15 Voltage and Frequency Protection 27/59 Under/Overvoltage Overexcitation Protection, Jump of 64/59N Displacement Voltage Voltage Vector 81 U/O Under/Overfrequency, f< ,f> Overexcitation Protection Jump of Voltage Vector Phase Rotation 74TC Trip Circuit Supervision Lock out —...
  • Page 212: Accessories

    Appendix A.1 Ordering Information and Accessories A.1.2 Accessories Exchangeable interface modules Name Order No. RS232 C53207-A351-D641-1 RS485 C53207-A351-D642-1 FO 820 nm C53207-A351-D643-1 Profibus DP RS485 C53207-A351-D611-1 Profibus DP double ring C53207-A351-D613-1 Modbus RS485 C53207-A351-D621-1 Modbus 820 nm C53207-A351-D623-1 DNP 3.0 RS 485 C53207-A351-D631-1 DNP 3.0 820 nm C53207-A351-D633-1...
  • Page 213: Terminal Assignments

    Appendix A.2 Terminal Assignments Terminal Assignments A.2.1 7RW80 — Housing for Panel Flush Mounting or Cubicle Mounting 7RW801* Figure A-1 General diagram 7RW801 SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 214: 7Rw80 - Housing For Panel Surface Mounting

    Appendix A.2 Terminal Assignments A.2.2 7RW80 — Housing for panel surface mounting 7RW802 Figure A-2 General diagram 7RW802 SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 215: Connection Examples

    Appendix A.3 Connection Examples Connection Examples Figure A-3 Example for connection type "VAN, VBN, VCN" load-side voltage connection Figure A-4 Voltage transformer connections to two voltage transformers (phase-to-phase voltages) and broken delta winding (da-dn) – appropriate for all networks SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 216 Appendix A.3 Connection Examples Figure A-5 Example for connection type "Vph-n, Vsyn" The connection can be established at any one of the three phases. The phase must be the same for Vph-n and Vsyn. Figure A-6 Example for connection type "VAB, VBC, Vx" SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 217 Appendix A.3 Connection Examples Figure A-7 Example for connection type "VAB, VBC" Figure A-8 Example for connection type "VAB, VBC" with phase voltage connection as open-delta connec- tion Figure A-9 Example for connection type "VAB, VBC, VSYN" SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 218 Appendix A.3 Connection Examples Figure A-10 Example for connection type "VAB, VBC, VSYN" with phase voltage connection as open-delta connection SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 219: Default Settings

    Appendix A.4 Default Settings Default Settings A.4.1 LEDs Table A-1 Preset LED displays LEDs Default function Function No. Description LED1 Relay TRIP Relay GENERAL TRIP command LED2 Not configured No Function configured LED3 Not configured No Function configured LED4 Not configured No Function configured LED5 Not configured...
  • Page 220: Binary Output

    Appendix A.4 Default Settings A.4.3 Binary Output Table A-4 Output Relay Presettings for All Devices and Ordering Variants Binary Output Default function Function No. Description Relay TRIP Relay GENERAL TRIP command 52Breaker 52 Breaker 52Breaker 52 Breaker 52Breaker 52 Breaker Fail V balance Failure: Voltage Balance Fail Ph.
  • Page 221: Default Display

    Appendix A.4 Default Settings A.4.5 Default Display The start page of the default display, which will open after device startup, can be selected via parameter 640Start image DD. 6-line Display Figure A-11 Default display of 7RW80 Depending on the V- connection different default dispalys are visible Setting Parameter 213 VT Connect.
  • Page 222 Appendix A.4 Default Settings Spontaneous Fault Display After a fault has occurred, the most important fault data are automatically displayed after general device pickup in the order shown in the picture below. Figure A-12 Representation of spontaneous messages on the device display SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 223: Protocol-Dependent Functions

    Appendix A.5 Protocol-dependent Functions Protocol-dependent Functions Protocol → IEC 60870-5-103 IEC 61850 Ether- Profibus DP DNP3.0 net (EN 100) Modbus ASCII/RTU Function ↓ Operational Measured Values Metered Values Fault Recording Remote Protection Setting User-defined Indications and Switching Objects Time Synchronization Messages with Time Stamp Yes Commissioning Aids Measured Value Indication...
  • Page 224: Functional Scope

    Appendix A.6 Functional Scope Functional Scope Addr. Parameter Setting Options Default Setting Comments Grp Chge OPTION Disabled Disabled Setting Group Change Option Enabled OSC. FAULT REC. Disabled Enabled Oscillographic Fault Records Enabled 24 V/f Disabled Disabled 24 Overexcit. Protection Enabled (Volt/Hertz) VECTOR JUMP Disabled...
  • Page 225: Settings

    Appendix A.7 Settings Settings Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". Addr. Parameter Function Setting Options Default Setting Comments FLEXIBLE FUNC. Flexible Function Alarm Only OPERRAT. MODE 3-phase 3-phase Mode of Operation 1-phase no reference MEAS.
  • Page 226 Appendix A.7 Settings Addr. Parameter Function Setting Options Default Setting Comments VT Connect. 3ph P.System Data 1 Van, Vbn, Vcn Van, Vbn, Vcn VT Connection, three-phase Vab, Vbc, VGnd Vab, Vbc, VSyn Vab, Vbc Vph-g, VSyn Vab, Vbc, Vx Rated Frequency P.System Data 1 50 Hz 50 Hz...
  • Page 227 Appendix A.7 Settings Addr. Parameter Function Setting Options Default Setting Comments 4304 24-2 PICKUP 24 V/f Overflux 1.00 .. 1.40 1.40 24-2 V/f Pickup 4305 24-2 DELAY 24 V/f Overflux 0.00 .. 60.00 sec; ∞ 1.00 sec 24-2 V/f Time Delay 4306 24-t(V/f=1.05) 24 V/f Overflux...
  • Page 228 Appendix A.7 Settings Addr. Parameter Function Setting Options Default Setting Comments 5131 27 Vp< 27/59 O/U Volt. 10 .. 120 V 45 V 27 Pickup Vp< 5132 27 T Vp< 27/59 O/U Volt. 0.1 .. 5.0 sec 1.0 sec 27 T Vp< Time Delay 5133 Pickup - Time 27/59 O/U Volt.
  • Page 229 Appendix A.7 Settings Addr. Parameter Function Setting Options Default Setting Comments 5529 LR1 after 81-2 Load Restore Load restoration element 1 after 81- 5530 LR1 after 81-3 Load Restore Load restoration element 1 after 81- 5531 LR1 after 81-4 Load Restore Load restoration element 1 after 81- 5540 Load Restore...
  • Page 230 Appendix A.7 Settings Addr. Parameter Function Setting Options Default Setting Comments 5588 LR4 after 81-1 Load Restore Load restoration element 4 after 81- 5589 LR4 after 81-2 Load Restore Load restoration element 4 after 81- 5590 LR4 after 81-3 Load Restore Load restoration element 4 after 81- 5591 LR4 after 81-4...
  • Page 231: Information List

    Appendix A.8 Information List Information List Indications for IEC 60 870-5-103 are always reported ON / OFF if they are subject to general interrogation for IEC 60 870-5-103. If not, they are reported only as ON. New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON / OFF and subjected to general interrogation if the information type is not a spontaneous event („.._Ev“).
  • Page 232 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio Controlmode REMOTE (ModeR- Cntrl Authority IntSP EMOTE) Control Authority (Cntrl Auth) Cntrl Authority IntSP Controlmode LOCAL (ModeLO- Cntrl Authority IntSP CAL) 52 Breaker (52Breaker) Control Device CF_D 52 Breaker (52Breaker)
  • Page 233 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio >Setting Group Select Bit 0 (>Set Change Group LED BI Group Bit0) >Setting Group Select Bit 1 (>Set Change Group LED BI Group Bit1) 009.0100 Failure EN100 Modul (Failure...
  • Page 234 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 170.2007 25 Sync. Measuring request of SYNC function 1 Control (25 Measu. req.) 170.2008 >BLOCK 25-group 1 (>BLK 25-1) SYNC function 1 LED BI 170.2009 >25 Direct Command output...
  • Page 235 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 170.2092 25 fdiff too large (f2>f1) (25 f2>f1) SYNC function 1 170.2093 25 fdiff too large (f2<f1) (25 f2<f1) SYNC function 1 170.2094 25 alphadiff too large (a2>a1) (25 SYNC function 1...
  • Page 236 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 235.2119 Function $00 is switched OFF ($00 OFF) 235.2120 Function $00 is ACTIVE ($00 ACTIVE) 235.2121 Function $00 picked up ($00 picked up) 235.2122 Function $00 Pickup Phase A ($00 pickup A)
  • Page 237 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio Relay Drop Out (Relay Drop Out) Device, General General CLOSE of relay (Relay Device, General CLOSE) Relay GENERAL TRIP command P.System Data 2 (Relay TRIP) Time from Pickup to drop out (PU Device, General...
  • Page 238 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 5357 >24 Reset memory of thermal 24 V/f Overflux LED BI replica V/f (>24 RM th.repl.) 5361 24 is swiched OFF (24 OFF) 24 V/f Overflux 5362 24 is BLOCKED (24 BLOCKED)
  • Page 239 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 6537 27-2 Undervoltage picked up 27/59 O/U Volt. (27-2 picked up) 6538 27-2 Undervoltage PICKUP 27/59 O/U Volt. w/curr. superv (27-2 PU CS) 6539 27-1 Undervoltage TRIP (27-1 27/59 O/U Volt.
  • Page 240 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 17336 Load restoration Block (LR Block) Load Restore LED BI 17337 Load restoration break (LR Load Restore LED BI Break) 17338 Load restoration Process (LR Load Restore LED BI Process)
  • Page 241 Appendix A.8 Information List Description Function Type Log Buffers Configurable in Matrix IEC 60870-5-103 of In- for- matio 17371 >Block Overvoltage protection 27/59 O/U Volt. LED BI Vp> (>BLOCK Vp>) 17372 Vp< Undervoltage picked up 27/59 O/U Volt. (Vp< picked up) 17373 Vp>...
  • Page 242: Group Alarms

    Appendix A.9 Group Alarms Group Alarms Description Function No. Description Error Sum Alarm Fail Battery I/O-Board error 10080 Error Ext I/O 10081 Error Ethernet 10083 Error Basic I/O Error Offset Alarm NO calibr Alarm Sum Event Fail V balance Fail Ph. Seq. V Fail Ph.
  • Page 243: Measured Values

    Appendix A.10 Measured Values A.10 Measured Values Description Function IEC 60870-5-103 Configurable in Matrix Number of TRIPs= (#of TRIPs=) Statistics Operating hours greater than (OpHour>) SetPoint(Stat) 170.2050 V1 = (V1 =) SYNC function 1 170.2051 f1 = (f1 =) SYNC function 1 170.2052 V2 = (V2 =) SYNC function 1...
  • Page 244 Appendix A.10 Measured Values Description Function IEC 60870-5-103 Configurable in Matrix Pulsed Energy Wq (reactive) (Wq(puls)) Energy 30800 Voltage VX (VX =) Measurement 30801 Voltage phase-neutral (Vph-n =) Measurement ■ SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 245: Literature

    Literature SIPROTEC 4 System Description; E50417-H1100-C151-B1 SIPROTEC DIGSI, Start UP; E50417-G1100-C152-A3 DIGSI CFC, Manual; E50417-H1100-C098-A9 SIPROTEC SIGRA 4, Manual; E50417-H1176-C070-A4 SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 246 Literature SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 247: Glossary

    Glossary Battery The buffer battery ensures that specified data areas, flags, timers and counters are retained retentively. Bay controllers Bay controllers are devices with control and monitoring functions without protective functions. Bit pattern indication Bit pattern indication is a processing function by means of which items of digital process information applying across several inputs can be detected together in parallel and processed further.
  • Page 248 Glossary Combination matrix DIGSI V4.6 and higher allows up to 32 compatible SIPROTEC 4 devices to communicate with each other in an inter-relay communication network (IRC). The combination matrix defines which devices exchange which in- formation. Communication branch A communications branch corresponds to the configuration of 1 to n users which communicate by means of a common bus.
  • Page 249 Glossary Double command Double commands are process outputs which indicate 4 process states at 2 outputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions) Double-point indication Double-point indications are items of process information which indicate 4 process states at 2 inputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions).
  • Page 250 Glossary ExMV External metered value via an ETHERNET connection, device-specific ExSI External single-point indication via an ETHERNET connection, device-specific → Single-point indication ExSI_F External single point indication via an ETHERNET connection, device-specific, → Fleeting indication, → Single- point indication Field devices Generic term for all devices assigned to the field level: Protection devices, combination devices, bay control- lers.
  • Page 251 Glossary Grounding Grounding means that a conductive part is to connect via a grounding system to → ground. Grounding Grounding is the total of all means and measured used for grounding. Hierarchy level Within a structure with higher-level and lower-level objects a hierarchy level is a container of equivalent objects. HV field description The HV project description file contains details of fields which exist in a ModPara project.
  • Page 252 Glossary Initialization string An initialization string comprises a range of modem-specific commands. These are transmitted to the modem within the framework of modem initialization. The commands can, for example, force specific settings for the modem. Inter relay communication → IRC combination IRC combination Inter Relay Communication, IRC, is used for directly exchanging process information between SIPROTEC 4 devices.
  • Page 253 Glossary Master Masters may send data to other users and request data from other users. DIGSI operates as a master. Metered value Metered values are a processing function with which the total number of discrete similar events (counting pulses) is determined for a period, usually as an integrated value. In power supply companies the electrical work is usually recorded as a metered value (energy purchase/supply, energy transportation).
  • Page 254 Glossary Object properties Each object has properties. These might be general properties that are common to several objects. An object can also have specific properties. Off-line In offline mode a link with the SIPROTEC 4 device is not necessary. You work with data which are stored in files. OI_F Output indication fleeting →...
  • Page 255 Glossary Protection devices All devices with a protective function and no control display. Reorganizing Frequent addition and deletion of objects creates memory areas that can no longer be used. By cleaning up projects, you can release these memory areas. However, a clean up also reassigns the VD addresses. As a consequence, all SIPROTEC 4 devices need to be reinitialized.
  • Page 256 Glossary SICAM WinCC The SICAM WinCC operator control and monitoring system displays the condition of your network graphically, visualizes alarms and indications, archives the network data, allows to intervene manually in the process and manages the system rights of the individual employee. Single command Single commands are process outputs which indicate 2 process states (for example, ON/OFF) at one output.
  • Page 257 Glossary Tree view The left pane of the project window displays the names and symbols of all containers of a project in the form of a folder tree. This area is called the tree view. TxTap → Transformer Tap Indication User address A user address comprises the name of the station, the national code, the area code and the user-specific phone number.
  • Page 258 Glossary SIPROTEC, 7RW80, Manual C53000-G1140-C233-1, Release date 10.2010...
  • Page 259: Index

    Index AC voltage 176 Fault Display Analog inputs 176 Setting note 28 Auxiliary voltage 176 Fault Event Recording 201 Fault recording 34,202 Fiber-optic Cables 157 Final Preparation of the Device 173 Flexible Protective Functions 189 Frequency Decrease 50 Binary inputs 177 Frequency Increase 50 Binary outputs 177 Frequency Protection 50...
  • Page 260 Index Load Restoration 188 Local Measured Values Monitoring 202 Temperatures 183 Terminating the Trip Signal 113 Test: system interface 160 Test: Voltage transformer miniature circuit breaker (VT mcb) 168 Malfunction responses of monitoring equipment 77 Time Allocation 201 Measured value monitoring 68 Time Synchronization 202 Mechanical Stress Tests 182 Triggering Oscillographic Recording 172...

Table of Contents