Base Pan Heater Control (Optional); Three Way Valve Control - Philips WH-UD16CE5-A-1 Service Manual

Air-to-water hweatpump
Table of Contents

Advertisement

2
Booster heater Turn Off condition:
Tank temperature > Tank set temperature + [+2°C] for continuous 15 sec
o
When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank
o
heat-up interval
* DELAY TIMER can be set by control panel.

13.11 Base Pan Heater Control (Optional)

To enable the base pan heater function, pin 3 of SW2 of water system PCB has to be switched from OFF to ON
position.
Base pan heater ON condition:
1
When outdoor ambient temperature ≤ 3°C AND
2
Deice operation ON
Base pan heater will continue ON for 10 minutes after deice operation ends.
Base pan heater OFF condition:
1
When outdoor ambient temperature > 3°C OR
2
When operation is not heating OR
3
Base pan heater ON timer count completed

13.12 Three Way Valve Control

Purpose:
- 3 ways valve is used to change flow direction of hot water from heatpump between heating side and tank side
Control contents:
1
3 ways valve switch Off:
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
o
2
3 ways valve switch On:
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
o
3
Stop condition:
During stop mode, 3 ways valve will be in switch off position
o
86