Pf612 Transmission Word Count Setup - Toshiba 2000 User Manual

Integrated controller
Hide thumbs Also See for 2000:
Table of Contents

Advertisement

7.5 PF612 Transmission Word Count Setup

This procedure is used to set the PF612 module transmission word count.
It is valid only when setup from the controller is selected with the MODE2 setup switch
(MD7, MD6=ON, ON).
(1) Check that the PF module Healthy counter is changed. (If it is not changed, this request
is not accepted.)
(2) Write 0003h in the PF module control code.
(3) Write a value between 1 and 122 in PF612 transmit word count. (Note that the sum of
(3) and (4) must not exceed 208)
(4) Write a value between 1 and 122 in PF612 receive word count. (Note that the sum of
(3) and (4) must not exceed 208)
(5) Write A5A5h in the PF module control enable flag.
(6) Check that the PF612 transmission word count setup request acknowledge result is 1
to confirm the end of setup.
The PF module control enable flag and the PF module control code are cleared when the
PF module processes this request.
This request is accepted only once after a power on or PF module reset. If this request
ends abnormally, turn on the power or reset the PF module once more and set the correct
transmission word count.
6F8C1147
7.5 PF612 Transmission Word Count Setup
7
29

Advertisement

Table of Contents
loading

Table of Contents