Toshiba MMU-AP0072H2UL Engineering Data Book page 181

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
MMD-AP0724H2UL, MMD-AP0964H2UL
42.6"(1083) Outside
0.9"(22)
Air discharge port
1.8"(46)
2.6"(65)
Space required for installation or service work
Service
space
Distance from building
Service
space
Check port
23.6"(600)
1"(25)
Screw hole for duct mounting(17-M5)
0.6"(15)
Screw hole for duct mounting(17-M5)
Hole for hanging bolt
50.7"(1288) Hanging bolt mounting pitch
(4-Ø1/2"(12)×3.6"(92))
52.3"(1328)
Refrigerant pipe connecting port
(Gas side Ø7/8"(22.2) Brazed)
1"(25)
49.2"(1250)
0.6"(15)
Screw hole for duct mounting
(6-M5)
Drain pipe connecting port(V25)
Taper screw for R1,1"(25.4) pipes
Attention
Be sure to set the plug and to make it to be able to cleaning,
because garbage in drain piping piles up easily in drain trap.
Plug
(Check and cleaning port)
Check port
Ø1"(26) Hole for control wire
and remote control wiring
Ø7/8"(22.2) Hole for power supply cable
Z view
180
1"(25)
0.6"(15)
Electric parts box
Refrigerant pipe connecting port
(Liquid side Ø1/2"(12.7) Flared)
1"(25)
0.6"(15)
24.6"(624)
27.5"(698)
Screw hole for duct mounting
(6-M5)
<Note>
1. Indoor unit does not have air filter its inside.
So be sure to set an air filter (local
arrangements) in the position maintained
easily such as a suction grills.
Check panel
(If there is no air filter, dusts are blocked in the
air heat exchanger and it may cause failure or
water leak in air-conditioner.)
2. Leave sufficient space to remove the air filter
when you attach it.
Unit: in (mm)
7.8"(198.5)
3.6"(91.5)
42.6"(1083) Outside
Air suction port

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents