Fault Acknowledge (H6) - Panasonic EBL512 G3 User Manual

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01603 Rev: -
8
Menu
Print
Escape
menu

FAULT Acknowledge (H6)

LED "Fault tx activated" on the front (down to the left) is indicating
that the output for Fault condition routing equipment is activated.
The LED will be turned off when all faults are acknowledged.
LED "General fault" on the front (above LED "Fault tx activated") is
indicating that not all faults are acknowledged and corrected.
Up to 300 faults can be listed.
no status = not corrected / serviced and not acknowledged fault.
= not corrected / serviced but acknowledged fault.
/Acknowledged
= corrected / serviced but not acknowledged fault.
/Serviced
Press the Soft key "Menu".
With the keypad select 0, 1, 2 - - 8 or 9 for a User name.
Type the Password for that user name. (Six digits. * * * * * *)
H1 Perform monthly test
Press (  ) five times to highlight menu H6.
H6 FAULT Acknowledge
Press ( ).
This is a list, i.e. you can scroll in the list with (  ) or (  ).
The most recent fault is on top of the list. In case of many faults you
can use the Soft keys "Previous page" and "Next page"
respectively.
If a printer is available the Soft key "Print" is shown and can be used
to start a print-out. Print items from latest:
hour
day
week
month
All
Scroll in the list with (  ) or (  ) and select. Press ( ).
Select the fault to be acknowledged. The selected fault has a frame.
Press ( ) to acknowledge the selected fault.
NOTE!
A fault that is both serviced and acknowledged will
disappear from the list.
➐ To leave a menu press ESC
To leave the menu system press the Soft key "Escape menu".
EBL512 G3 version 2.0.x, Daily user's manual